⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 200 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)10 AWG5.26 mm² · Drop: 2.24%
Aluminum Wire (≤3% Drop)8 AWGDrop: 11.13V (2.32%)
Voltage at Load End469.3 VLoss: 10.74 V (465.0 W)
Power & Breaker (125%)20.78 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 200 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A27.16 V (5.66%)452.8 V44.8 V (9.33%)1176.0 WDrop/Amp High
12 AWG3.31 mm²20 A17.07 V (3.56%)462.9 V28.15 V (5.86%)739.0 WDrop/Amp High
10 AWG5.26 mm²30 A10.74 V (2.24%)469.3 V17.71 V (3.69%)465.0 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A6.75 V (1.41%)473.3 V11.13 V (2.32%)292.2 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A4.25 V (0.88%)475.8 V7.01 V (1.46%)183.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.67 V (0.56%)477.3 V4.41 V (0.92%)115.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.12 V (0.44%)477.9 V3.49 V (0.73%)91.7 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.68 V (0.35%)478.3 V2.77 V (0.58%)72.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.33 V (0.28%)478.7 V2.2 V (0.46%)57.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.06 V (0.22%)478.9 V1.74 V (0.36%)45.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.84 V (0.17%)479.2 V1.38 V (0.29%)36.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.66 V (0.14%)479.3 V1.1 V (0.23%)28.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.53 V (0.11%)479.5 V0.87 V (0.18%)22.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.45 V (0.09%)479.6 V0.74 V (0.15%)19.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.37 V (0.08%)479.6 V0.61 V (0.13%)16.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.32 V (0.07%)479.7 V0.53 V (0.11%)13.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.28 V (0.06%)479.7 V0.46 V (0.1%)12.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.22 V (0.05%)479.8 V0.37 V (0.08%)9.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.19 V (0.04%)479.8 V0.31 V (0.06%)8.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.15 V (0.03%)479.9 V0.25 V (0.05%)6.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.11 V (0.02%)479.9 V0.18 V (0.04%)4.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 200 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 200 feet one-way at 480V (3-Phase), you need 10 AWG copper wire. This produces a voltage drop of 10.74V (2.24%) and delivers 469.3V at the load.

What size aluminum wire is required for 25 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 11.13V (2.32%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.