🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)4 AWGDrop: 6.06V (2.91%)
Voltage at Load End202.2 VLoss: 5.84 V (252.9 W)
Power & Breaker (125%)9.01 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A37.34 V (17.95%)170.7 V61.6 V (29.61%)1617.0 WDrop/Amp High
12 AWG3.31 mm²20 A23.47 V (11.28%)184.5 V38.71 V (18.61%)1016.1 WDrop/Amp High
10 AWG5.26 mm²30 A14.77 V (7.1%)193.2 V24.36 V (11.71%)639.4 WDrop/Amp High
8 AWG8.37 mm²50 A9.28 V (4.46%)198.7 V15.31 V (7.36%)401.8 W~ ≤5%
6 AWG13.3 mm²65 A5.84 V (2.81%)202.2 V9.63 V (4.63%)252.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.67 V (1.77%)204.3 V6.06 V (2.91%)159.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.91 V (1.4%)205.1 V4.8 V (2.31%)126.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.31 V (1.11%)205.7 V3.81 V (1.83%)100.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.83 V (0.88%)206.2 V3.02 V (1.45%)79.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.45 V (0.7%)206.5 V2.4 V (1.15%)62.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.15 V (0.55%)206.8 V1.9 V (0.91%)49.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.91 V (0.44%)207.1 V1.51 V (0.72%)39.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.72 V (0.35%)207.3 V1.2 V (0.57%)31.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.61 V (0.29%)207.4 V1.01 V (0.49%)26.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.51 V (0.25%)207.5 V0.84 V (0.41%)22.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.44 V (0.21%)207.6 V0.72 V (0.35%)19.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.38 V (0.18%)207.6 V0.63 V (0.3%)16.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.31 V (0.15%)207.7 V0.51 V (0.24%)13.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.26 V (0.12%)207.7 V0.42 V (0.2%)11.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.2 V (0.1%)207.8 V0.34 V (0.16%)8.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.15 V (0.07%)207.8 V0.25 V (0.12%)6.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 275 feet one-way at 208V (3-Phase), you need 6 AWG copper wire. This produces a voltage drop of 5.84V (2.81%) and delivers 202.2V at the load.

What size aluminum wire is required for 25 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 6.06V (2.91%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.