🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 400 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.86%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.42V (3.54%)
Voltage at Load End11.7 VLoss: 0.34 V (8.6 W)
Power & Breaker (125%)0.3 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 400 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A62.72 V (522.65%)0.0 V103.46 V (862.13%)1568.0 WDrop/Amp High
12 AWG3.31 mm²20 A39.41 V (328.44%)0.0 V65.01 V (541.76%)985.3 WDrop/Amp High
10 AWG5.26 mm²30 A24.8 V (206.68%)0.0 V40.91 V (340.92%)620.0 WDrop/Amp High
8 AWG8.37 mm²50 A15.59 V (129.88%)0.0 V25.71 V (214.25%)389.6 WDrop/Amp High
6 AWG13.3 mm²65 A9.81 V (81.74%)2.2 V16.18 V (134.83%)245.2 WDrop/Amp High
4 AWG21.15 mm²85 A6.17 V (51.4%)5.8 V10.17 V (84.79%)154.2 WDrop/Amp High
3 AWG26.67 mm²100 A4.89 V (40.76%)7.1 V8.07 V (67.24%)122.3 WDrop/Amp High
2 AWG33.62 mm²115 A3.88 V (32.34%)8.1 V6.4 V (53.34%)97.0 WDrop/Amp High
1 AWG42.41 mm²130 A3.08 V (25.63%)8.9 V5.07 V (42.28%)76.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.44 V (20.32%)9.6 V4.02 V (33.52%)61.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.93 V (16.12%)10.1 V3.19 V (26.59%)48.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.53 V (12.79%)10.5 V2.53 V (21.09%)38.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.22 V (10.14%)10.8 V2.01 V (16.73%)30.4 WDrop/Amp High
250 kcmil126.7 mm²255 A1.03 V (8.58%)11.0 V1.7 V (14.15%)25.7 WDrop/Amp High
300 kcmil152.0 mm²285 A0.86 V (7.15%)11.1 V1.42 V (11.8%)21.5 WDrop/Amp High
350 kcmil177.3 mm²310 A0.74 V (6.13%)11.3 V1.21 V (10.11%)18.4 WDrop/Amp High
400 kcmil202.7 mm²335 A0.64 V (5.36%)11.4 V1.06 V (8.85%)16.1 WDrop/Amp High
500 kcmil253.4 mm²380 A0.51 V (4.29%)11.5 V0.85 V (7.08%)12.9 W~ ≤5%
600 kcmil304.0 mm²420 A0.43 V (3.58%)11.6 V0.71 V (5.9%)10.7 W~ ≤5%
750 kcmil380.0 mm²475 A0.34 V (2.86%)11.7 V0.57 V (4.72%)8.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.26 V (2.15%)11.7 V0.42 V (3.54%)6.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 400 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 400 feet one-way at 12V (DC), you need 750 kcmil copper wire. This produces a voltage drop of 0.34V (2.86%) and delivers 11.7V at the load.

What size aluminum wire is required for 25 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.42V (3.54%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.