🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

25 Amp Wire Size at 500 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 25 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.53V (4.42%)
Voltage at Load End11.7 VLoss: 0.32 V (8.0 W)
Power & Breaker (125%)0.3 kW32A Breaker Recommended

All AWG & kcmil Wire Gauges for 25 Amps at 500 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A78.4 V (653.32%)0.0 V129.32 V (1077.67%)1960.0 WDrop/Amp High
12 AWG3.31 mm²20 A49.27 V (410.54%)0.0 V81.26 V (677.21%)1231.6 WDrop/Amp High
10 AWG5.26 mm²30 A31.0 V (258.35%)0.0 V51.14 V (426.15%)775.0 WDrop/Amp High
8 AWG8.37 mm²50 A19.48 V (162.35%)0.0 V32.14 V (267.81%)487.1 WDrop/Amp High
6 AWG13.3 mm²65 A12.26 V (102.17%)0.0 V20.22 V (168.54%)306.5 WDrop/Amp High
4 AWG21.15 mm²85 A7.71 V (64.25%)4.3 V12.72 V (105.98%)192.8 WDrop/Amp High
3 AWG26.67 mm²100 A6.11 V (50.95%)5.9 V10.09 V (84.05%)152.9 WDrop/Amp High
2 AWG33.62 mm²115 A4.85 V (40.42%)7.1 V8.0 V (66.67%)121.3 WDrop/Amp High
1 AWG42.41 mm²130 A3.85 V (32.04%)8.2 V6.34 V (52.85%)96.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.05 V (25.4%)9.0 V5.03 V (41.91%)76.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.42 V (20.15%)9.6 V3.99 V (33.24%)60.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.92 V (15.99%)10.1 V3.16 V (26.37%)48.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.52 V (12.68%)10.5 V2.51 V (20.91%)38.0 WDrop/Amp High
250 kcmil126.7 mm²255 A1.29 V (10.73%)10.7 V2.12 V (17.69%)32.2 WDrop/Amp High
300 kcmil152.0 mm²285 A1.07 V (8.94%)10.9 V1.77 V (14.75%)26.8 WDrop/Amp High
350 kcmil177.3 mm²310 A0.92 V (7.66%)11.1 V1.52 V (12.64%)23.0 WDrop/Amp High
400 kcmil202.7 mm²335 A0.8 V (6.7%)11.2 V1.33 V (11.06%)20.1 WDrop/Amp High
500 kcmil253.4 mm²380 A0.64 V (5.36%)11.4 V1.06 V (8.85%)16.1 WDrop/Amp High
600 kcmil304.0 mm²420 A0.54 V (4.47%)11.5 V0.88 V (7.37%)13.4 W~ ≤5%
750 kcmil380.0 mm²475 A0.43 V (3.58%)11.6 V0.71 V (5.9%)10.7 W~ ≤5%
1000 kcmil506.7 mm²545 A0.32 V (2.68%)11.7 V0.53 V (4.42%)8.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 25 amps at 500 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 25A load over 500 feet one-way at 12V (DC), you need 1000 kcmil copper wire. This produces a voltage drop of 0.32V (2.68%) and delivers 11.7V at the load.

What size aluminum wire is required for 25 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.53V (4.42%).

What breaker size is needed for a 25A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (25A × 1.25 = 31.2A), which corresponds to a standard 32A circuit breaker.