⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 250 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.32%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 6.57V (2.74%)
Voltage at Load End234.4 VLoss: 5.57 V (2413.2 W)
Power & Breaker (125%)103.92 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A339.47 V (141.45%)0.0 V559.97 V (233.32%)146996.4 WDrop/Amp High
12 AWG3.31 mm²20 A213.32 V (88.89%)26.7 V351.89 V (146.62%)92372.4 WDrop/Amp High
10 AWG5.26 mm²30 A134.24 V (55.93%)105.8 V221.43 V (92.26%)58127.9 WDrop/Amp High
8 AWG8.37 mm²50 A84.36 V (35.15%)155.6 V139.16 V (57.98%)36529.6 WDrop/Amp High
6 AWG13.3 mm²65 A53.09 V (22.12%)186.9 V87.57 V (36.49%)22988.9 WDrop/Amp High
4 AWG21.15 mm²85 A33.39 V (13.91%)206.6 V55.07 V (22.95%)14456.4 WDrop/Amp High
3 AWG26.67 mm²100 A26.48 V (11.03%)213.5 V43.67 V (18.2%)11464.3 WDrop/Amp High
2 AWG33.62 mm²115 A21.0 V (8.75%)219.0 V34.64 V (14.44%)9094.4 WDrop/Amp High
1 AWG42.41 mm²130 A16.65 V (6.94%)223.4 V27.46 V (11.44%)7209.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.2 V (5.5%)226.8 V21.77 V (9.07%)5716.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.47 V (4.36%)229.5 V17.27 V (7.2%)4534.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.31 V (3.46%)231.7 V13.7 V (5.71%)3596.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.59 V (2.74%)233.4 V10.87 V (4.53%)2852.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.57 V (2.32%)234.4 V9.19 V (3.83%)2413.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.65 V (1.94%)235.4 V7.66 V (3.19%)2011.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.98 V (1.66%)236.0 V6.57 V (2.74%)1724.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.48 V (1.45%)236.5 V5.75 V (2.39%)1508.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.79 V (1.16%)237.2 V4.6 V (1.92%)1206.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.32 V (0.97%)237.7 V3.83 V (1.6%)1005.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.86 V (0.77%)238.1 V3.07 V (1.28%)804.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.39 V (0.58%)238.6 V2.3 V (0.96%)603.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 250 feet one-way at 240V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 5.57V (2.32%) and delivers 234.4V at the load.

What size aluminum wire is required for 250 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 6.57V (2.74%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.