🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

250 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 250 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 1.28%
Aluminum Wire (≤3% Drop)350 kcmilDrop: 7.23V (1.51%)
Voltage at Load End473.9 VLoss: 6.13 V (2654.5 W)
Power & Breaker (125%)207.85 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 250 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A373.42 V (77.8%)106.6 V615.97 V (128.33%)161696.0 WDrop/Amp High
12 AWG3.31 mm²20 A234.66 V (48.89%)245.3 V387.07 V (80.64%)101609.6 WDrop/Amp High
10 AWG5.26 mm²30 A147.66 V (30.76%)332.3 V243.58 V (50.75%)63940.6 WDrop/Amp High
8 AWG8.37 mm²50 A92.8 V (19.33%)387.2 V153.07 V (31.89%)40182.5 WDrop/Amp High
6 AWG13.3 mm²65 A58.4 V (12.17%)421.6 V96.33 V (20.07%)25287.8 WDrop/Amp High
4 AWG21.15 mm²85 A36.72 V (7.65%)443.3 V60.58 V (12.62%)15902.0 WDrop/Amp High
3 AWG26.67 mm²100 A29.12 V (6.07%)450.9 V48.04 V (10.01%)12610.7 WDrop/Amp High
2 AWG33.62 mm²115 A23.1 V (4.81%)456.9 V38.11 V (7.94%)10003.8 WDrop/Amp High
1 AWG42.41 mm²130 A18.31 V (3.82%)461.7 V30.21 V (6.29%)7930.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.52 V (3.03%)465.5 V23.95 V (4.99%)6287.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.52 V (2.4%)468.5 V19.0 V (3.96%)4987.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.14 V (1.9%)470.9 V15.07 V (3.14%)3956.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.25 V (1.51%)472.8 V11.95 V (2.49%)3137.4 WDrop/Amp High
250 kcmil126.7 mm²255 A6.13 V (1.28%)473.9 V10.11 V (2.11%)2654.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A5.11 V (1.06%)474.9 V8.43 V (1.76%)2212.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.38 V (0.91%)475.6 V7.23 V (1.51%)1896.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.83 V (0.8%)476.2 V6.32 V (1.32%)1659.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.07 V (0.64%)476.9 V5.06 V (1.05%)1327.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.55 V (0.53%)477.4 V4.21 V (0.88%)1106.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.04 V (0.43%)478.0 V3.37 V (0.7%)885.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.53 V (0.32%)478.5 V2.53 V (0.53%)663.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 250 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 250A load over 275 feet one-way at 480V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 6.13V (1.28%) and delivers 473.9V at the load.

What size aluminum wire is required for 250 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 350 kcmil to maintain voltage drop at 7.23V (1.51%).

What breaker size is needed for a 250A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (250A × 1.25 = 312.5A), which corresponds to a standard 350A circuit breaker.