⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 300 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 1.28%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 6.07V (1.26%)
Voltage at Load End473.9 VLoss: 6.13 V (2920.7 W)
Power & Breaker (125%)228.63 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 300 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A448.11 V (93.36%)31.9 V739.16 V (153.99%)213438.8 WDrop/Amp High
12 AWG3.31 mm²20 A281.59 V (58.66%)198.4 V464.49 V (96.77%)134124.7 WDrop/Amp High
10 AWG5.26 mm²30 A177.2 V (36.92%)302.8 V292.29 V (60.89%)84401.6 WDrop/Amp High
8 AWG8.37 mm²50 A111.36 V (23.2%)368.6 V183.69 V (38.27%)53040.9 WDrop/Amp High
6 AWG13.3 mm²65 A70.08 V (14.6%)409.9 V115.6 V (24.08%)33379.9 WDrop/Amp High
4 AWG21.15 mm²85 A44.07 V (9.18%)435.9 V72.69 V (15.14%)20990.7 WDrop/Amp High
3 AWG26.67 mm²100 A34.95 V (7.28%)445.1 V57.65 V (12.01%)16646.1 WDrop/Amp High
2 AWG33.62 mm²115 A27.72 V (5.78%)452.3 V45.73 V (9.53%)13205.0 WDrop/Amp High
1 AWG42.41 mm²130 A21.98 V (4.58%)458.0 V36.25 V (7.55%)10468.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.42 V (3.63%)462.6 V28.74 V (5.99%)8299.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.82 V (2.88%)466.2 V22.8 V (4.75%)6583.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.96 V (2.28%)469.0 V18.09 V (3.77%)5222.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.69 V (1.81%)471.3 V14.34 V (2.99%)4141.3 WDrop/Amp High
250 kcmil126.7 mm²255 A7.36 V (1.53%)472.6 V12.13 V (2.53%)3504.0 WDrop/Amp High
300 kcmil152.0 mm²285 A6.13 V (1.28%)473.9 V10.11 V (2.11%)2920.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A5.26 V (1.1%)474.7 V8.67 V (1.81%)2504.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A4.6 V (0.96%)475.4 V7.58 V (1.58%)2190.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.68 V (0.77%)476.3 V6.07 V (1.26%)1752.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.07 V (0.64%)476.9 V5.06 V (1.05%)1460.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.45 V (0.51%)477.5 V4.05 V (0.84%)1168.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.84 V (0.38%)478.2 V3.03 V (0.63%)876.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 300 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 300 feet one-way at 480V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 6.13V (1.28%) and delivers 473.9V at the load.

What size aluminum wire is required for 275 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 6.07V (1.26%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.