🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 350 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 1.49%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 7.08V (1.47%)
Voltage at Load End472.8 VLoss: 7.15 V (3407.5 W)
Power & Breaker (125%)228.63 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 350 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A522.79 V (108.91%)0.0 V862.36 V (179.66%)249011.9 WDrop/Amp High
12 AWG3.31 mm²20 A328.52 V (68.44%)151.5 V541.9 V (112.9%)156478.8 WDrop/Amp High
10 AWG5.26 mm²30 A206.73 V (43.07%)273.3 V341.01 V (71.04%)98468.6 WDrop/Amp High
8 AWG8.37 mm²50 A129.92 V (27.07%)350.1 V214.3 V (44.65%)61881.1 WDrop/Amp High
6 AWG13.3 mm²65 A81.76 V (17.03%)398.2 V134.87 V (28.1%)38943.2 WDrop/Amp High
4 AWG21.15 mm²85 A51.41 V (10.71%)428.6 V84.81 V (17.67%)24489.1 WDrop/Amp High
3 AWG26.67 mm²100 A40.77 V (8.49%)439.2 V67.26 V (14.01%)19420.5 WDrop/Amp High
2 AWG33.62 mm²115 A32.34 V (6.74%)447.7 V53.35 V (11.12%)15405.9 WDrop/Amp High
1 AWG42.41 mm²130 A25.64 V (5.34%)454.4 V42.29 V (8.81%)12212.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.33 V (4.24%)459.7 V33.53 V (6.99%)9683.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.13 V (3.36%)463.9 V26.6 V (5.54%)7681.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.79 V (2.66%)467.2 V21.1 V (4.4%)6092.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.14 V (2.11%)469.9 V16.73 V (3.49%)4831.6 WDrop/Amp High
250 kcmil126.7 mm²255 A8.58 V (1.79%)471.4 V14.16 V (2.95%)4088.0 WDrop/Amp High
300 kcmil152.0 mm²285 A7.15 V (1.49%)472.8 V11.8 V (2.46%)3407.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A6.13 V (1.28%)473.9 V10.12 V (2.11%)2921.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A5.36 V (1.12%)474.6 V8.85 V (1.84%)2555.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A4.29 V (0.89%)475.7 V7.08 V (1.47%)2044.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.58 V (0.75%)476.4 V5.9 V (1.23%)1703.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.86 V (0.6%)477.1 V4.72 V (0.98%)1363.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.15 V (0.45%)477.9 V3.54 V (0.74%)1022.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 350 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 350 feet one-way at 480V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 7.15V (1.49%) and delivers 472.8V at the load.

What size aluminum wire is required for 275 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 7.08V (1.47%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.