🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

275 Amp Wire Size at 450 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 275 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 1.92%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 9.1V (1.9%)
Voltage at Load End470.8 VLoss: 9.2 V (4381.1 W)
Power & Breaker (125%)228.63 kW350A Breaker Recommended

All AWG & kcmil Wire Gauges for 275 Amps at 450 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A672.16 V (140.03%)0.0 V1108.75 V (230.99%)320158.1 WDrop/Amp High
12 AWG3.31 mm²20 A422.38 V (88.0%)57.6 V696.73 V (145.15%)201187.0 WDrop/Amp High
10 AWG5.26 mm²30 A265.8 V (55.37%)214.2 V438.44 V (91.34%)126602.5 WDrop/Amp High
8 AWG8.37 mm²50 A167.04 V (34.8%)313.0 V275.53 V (57.4%)79561.4 WDrop/Amp High
6 AWG13.3 mm²65 A105.12 V (21.9%)374.9 V173.4 V (36.12%)50069.8 WDrop/Amp High
4 AWG21.15 mm²85 A66.1 V (13.77%)413.9 V109.04 V (22.72%)31486.0 WDrop/Amp High
3 AWG26.67 mm²100 A52.42 V (10.92%)427.6 V86.47 V (18.01%)24969.2 WDrop/Amp High
2 AWG33.62 mm²115 A41.59 V (8.66%)438.4 V68.6 V (14.29%)19807.5 WDrop/Amp High
1 AWG42.41 mm²130 A32.97 V (6.87%)447.0 V54.38 V (11.33%)15702.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A26.14 V (5.45%)453.9 V43.11 V (8.98%)12449.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.73 V (4.32%)459.3 V34.2 V (7.13%)9875.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.45 V (3.43%)463.6 V27.13 V (5.65%)7833.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.04 V (2.72%)467.0 V21.51 V (4.48%)6212.0 WDrop/Amp High
250 kcmil126.7 mm²255 A11.03 V (2.3%)469.0 V18.2 V (3.79%)5256.0 WDrop/Amp High
300 kcmil152.0 mm²285 A9.2 V (1.92%)470.8 V15.17 V (3.16%)4381.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A7.89 V (1.64%)472.1 V13.01 V (2.71%)3755.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A6.9 V (1.44%)473.1 V11.38 V (2.37%)3285.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A5.52 V (1.15%)474.5 V9.1 V (1.9%)2628.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.6 V (0.96%)475.4 V7.59 V (1.58%)2190.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.68 V (0.77%)476.3 V6.07 V (1.26%)1752.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.76 V (0.57%)477.2 V4.55 V (0.95%)1314.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 275 amps at 450 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 275A load over 450 feet one-way at 480V (3-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 9.2V (1.92%) and delivers 470.8V at the load.

What size aluminum wire is required for 275 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 9.1V (1.9%).

What breaker size is needed for a 275A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (275A × 1.25 = 343.8A), which corresponds to a standard 350A circuit breaker.