⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

300 Amp Wire Size at 450 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 300 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.73V (2.39%)
Voltage at Load End233.0 VLoss: 6.95 V (2085.0 W)
Power & Breaker (125%)72.0 kW400A Breaker Recommended

All AWG & kcmil Wire Gauges for 300 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A846.7 V (352.79%)0.0 V1396.66 V (581.94%)254009.8 WDrop/Amp High
12 AWG3.31 mm²20 A532.06 V (221.69%)0.0 V877.66 V (365.69%)159619.4 WDrop/Amp High
10 AWG5.26 mm²30 A334.82 V (139.51%)0.0 V552.29 V (230.12%)100444.9 WDrop/Amp High
8 AWG8.37 mm²50 A210.41 V (87.67%)29.6 V347.08 V (144.62%)63123.1 WDrop/Amp High
6 AWG13.3 mm²65 A132.42 V (55.17%)107.6 V218.42 V (91.01%)39724.8 WDrop/Amp High
4 AWG21.15 mm²85 A83.27 V (34.7%)156.7 V137.35 V (57.23%)24980.6 WDrop/Amp High
3 AWG26.67 mm²100 A66.03 V (27.51%)174.0 V108.93 V (45.39%)19810.3 WDrop/Amp High
2 AWG33.62 mm²115 A52.38 V (21.83%)187.6 V86.41 V (36.0%)15715.1 WDrop/Amp High
1 AWG42.41 mm²130 A41.53 V (17.3%)198.5 V68.5 V (28.54%)12457.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A32.92 V (13.72%)207.1 V54.31 V (22.63%)9877.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A26.12 V (10.88%)213.9 V43.08 V (17.95%)7835.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A20.72 V (8.63%)219.3 V34.17 V (14.24%)6215.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A16.43 V (6.85%)223.6 V27.1 V (11.29%)4928.5 WDrop/Amp High
250 kcmil126.7 mm²255 A13.9 V (5.79%)226.1 V22.93 V (9.55%)4170.0 WDrop/Amp High
300 kcmil152.0 mm²285 A11.59 V (4.83%)228.4 V19.11 V (7.96%)3475.9 WDrop/Amp High
350 kcmil177.3 mm²310 A9.93 V (4.14%)230.1 V16.38 V (6.83%)2979.9 W~ ≤5%
400 kcmil202.7 mm²335 A8.69 V (3.62%)231.3 V14.33 V (5.97%)2606.5 W~ ≤5%
500 kcmil253.4 mm²380 A6.95 V (2.9%)233.0 V11.46 V (4.78%)2085.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A5.79 V (2.41%)234.2 V9.56 V (3.98%)1738.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.63 V (1.93%)235.4 V7.64 V (3.19%)1390.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.48 V (1.45%)236.5 V5.73 V (2.39%)1042.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 300 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 300A load over 450 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 6.95V (2.9%) and delivers 233.0V at the load.

What size aluminum wire is required for 300 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.73V (2.39%).

What breaker size is needed for a 300A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (300A × 1.25 = 375.0A), which corresponds to a standard 400A circuit breaker.