🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.85%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 4.48V (0.93%)
Voltage at Load End475.9 VLoss: 4.08 V (2294.3 W)
Power & Breaker (125%)270.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A397.18 V (82.75%)82.8 V655.17 V (136.49%)223581.5 WDrop/Amp High
12 AWG3.31 mm²20 A249.59 V (52.0%)230.4 V411.71 V (85.77%)140498.4 WDrop/Amp High
10 AWG5.26 mm²30 A157.06 V (32.72%)322.9 V259.08 V (53.97%)88412.5 WDrop/Amp High
8 AWG8.37 mm²50 A98.7 V (20.56%)381.3 V162.81 V (33.92%)55561.5 WDrop/Amp High
6 AWG13.3 mm²65 A62.12 V (12.94%)417.9 V102.46 V (21.35%)34966.1 WDrop/Amp High
4 AWG21.15 mm²85 A39.06 V (8.14%)440.9 V64.43 V (13.42%)21988.2 WDrop/Amp High
3 AWG26.67 mm²100 A30.98 V (6.45%)449.0 V51.1 V (10.65%)17437.2 WDrop/Amp High
2 AWG33.62 mm²115 A24.57 V (5.12%)455.4 V40.53 V (8.44%)13832.5 WDrop/Amp High
1 AWG42.41 mm²130 A19.48 V (4.06%)460.5 V32.13 V (6.69%)10965.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.44 V (3.22%)464.6 V25.48 V (5.31%)8694.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.25 V (2.55%)467.7 V20.21 V (4.21%)6896.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.72 V (2.02%)470.3 V16.03 V (3.34%)5470.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.71 V (1.61%)472.3 V12.71 V (2.65%)4338.1 WDrop/Amp High
250 kcmil126.7 mm²255 A6.52 V (1.36%)473.5 V10.76 V (2.24%)3670.5 WDrop/Amp High
300 kcmil152.0 mm²285 A5.44 V (1.13%)474.6 V8.97 V (1.87%)3059.5 WDrop/Amp High
350 kcmil177.3 mm²310 A4.66 V (0.97%)475.3 V7.69 V (1.6%)2623.0 WDrop/Amp High
400 kcmil202.7 mm²335 A4.08 V (0.85%)475.9 V6.72 V (1.4%)2294.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.26 V (0.68%)476.7 V5.38 V (1.12%)1835.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.72 V (0.57%)477.3 V4.48 V (0.93%)1529.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.17 V (0.45%)477.8 V3.59 V (0.75%)1223.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.63 V (0.34%)478.4 V2.69 V (0.56%)917.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 225 feet one-way at 480V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 4.08V (0.85%) and delivers 475.9V at the load.

What size aluminum wire is required for 325 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 4.48V (0.93%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.