🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 250 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 0.94%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 4.98V (1.04%)
Voltage at Load End475.5 VLoss: 4.53 V (2549.2 W)
Power & Breaker (125%)270.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 250 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A441.32 V (91.94%)38.7 V727.96 V (151.66%)248423.9 WDrop/Amp High
12 AWG3.31 mm²20 A277.32 V (57.78%)202.7 V457.45 V (95.3%)156109.3 WDrop/Amp High
10 AWG5.26 mm²30 A174.51 V (36.36%)305.5 V287.86 V (59.97%)98236.1 WDrop/Amp High
8 AWG8.37 mm²50 A109.67 V (22.85%)370.3 V180.9 V (37.69%)61735.0 WDrop/Amp High
6 AWG13.3 mm²65 A69.02 V (14.38%)411.0 V113.85 V (23.72%)38851.3 WDrop/Amp High
4 AWG21.15 mm²85 A43.4 V (9.04%)436.6 V71.59 V (14.91%)24431.3 WDrop/Amp High
3 AWG26.67 mm²100 A34.42 V (7.17%)445.6 V56.77 V (11.83%)19374.6 WDrop/Amp High
2 AWG33.62 mm²115 A27.3 V (5.69%)452.7 V45.04 V (9.38%)15369.5 WDrop/Amp High
1 AWG42.41 mm²130 A21.64 V (4.51%)458.4 V35.7 V (7.44%)12184.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.16 V (3.58%)462.8 V28.31 V (5.9%)9660.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.61 V (2.84%)466.4 V22.46 V (4.68%)7663.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.8 V (2.25%)469.2 V17.81 V (3.71%)6078.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.56 V (1.78%)471.4 V14.12 V (2.94%)4820.2 WDrop/Amp High
250 kcmil126.7 mm²255 A7.24 V (1.51%)472.8 V11.95 V (2.49%)4078.3 WDrop/Amp High
300 kcmil152.0 mm²285 A6.04 V (1.26%)474.0 V9.96 V (2.08%)3399.5 WDrop/Amp High
350 kcmil177.3 mm²310 A5.18 V (1.08%)474.8 V8.54 V (1.78%)2914.4 WDrop/Amp High
400 kcmil202.7 mm²335 A4.53 V (0.94%)475.5 V7.47 V (1.56%)2549.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.62 V (0.75%)476.4 V5.98 V (1.24%)2039.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.02 V (0.63%)477.0 V4.98 V (1.04%)1699.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.42 V (0.5%)477.6 V3.98 V (0.83%)1359.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.81 V (0.38%)478.2 V2.99 V (0.62%)1019.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 250 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 250 feet one-way at 480V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 4.53V (0.94%) and delivers 475.5V at the load.

What size aluminum wire is required for 325 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 4.98V (1.04%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.