⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 300 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)7× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.99%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.14V (34.51%)
Voltage at Load End11.6 VLoss: 0.36 V (116.5 W)
Power & Breaker (125%)3.9 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 300 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A611.5 V (5095.87%)0.0 V1008.7 V (8405.81%)198739.1 WDrop/Amp High
12 AWG3.31 mm²20 A384.27 V (3202.24%)0.0 V633.86 V (5282.2%)124887.4 WDrop/Amp High
10 AWG5.26 mm²30 A241.81 V (2015.1%)0.0 V398.88 V (3323.97%)78588.9 WDrop/Amp High
8 AWG8.37 mm²50 A151.96 V (1266.36%)0.0 V250.67 V (2088.9%)49388.0 WDrop/Amp High
6 AWG13.3 mm²65 A95.63 V (796.95%)0.0 V157.75 V (1314.59%)31081.0 WDrop/Amp High
4 AWG21.15 mm²85 A60.14 V (501.15%)0.0 V99.2 V (826.67%)19545.0 WDrop/Amp High
3 AWG26.67 mm²100 A47.69 V (397.43%)0.0 V78.67 V (655.57%)15499.7 WDrop/Amp High
2 AWG33.62 mm²115 A37.83 V (315.27%)0.0 V62.41 V (520.05%)12295.6 WDrop/Amp High
1 AWG42.41 mm²130 A29.99 V (249.93%)0.0 V49.47 V (412.26%)9747.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A23.78 V (198.16%)0.0 V39.22 V (326.87%)7728.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.86 V (157.19%)0.0 V31.12 V (259.29%)6130.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.96 V (124.68%)0.0 V24.68 V (205.67%)4862.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.87 V (98.88%)0.1 V19.57 V (163.1%)3856.1 WDrop/Amp High
250 kcmil126.7 mm²255 A10.04 V (83.66%)2.0 V16.56 V (138.0%)3262.6 WDrop/Amp High
300 kcmil152.0 mm²285 A8.37 V (69.73%)3.6 V13.8 V (115.03%)2719.6 WDrop/Amp High
350 kcmil177.3 mm²310 A7.17 V (59.78%)4.8 V11.83 V (98.61%)2331.5 WDrop/Amp High
400 kcmil202.7 mm²335 A6.27 V (52.29%)5.7 V10.35 V (86.26%)2039.4 WDrop/Amp High
500 kcmil253.4 mm²380 A5.02 V (41.83%)7.0 V8.28 V (69.0%)1631.3 WDrop/Amp High
600 kcmil304.0 mm²420 A4.18 V (34.87%)7.8 V6.9 V (57.51%)1359.8 WDrop/Amp High
750 kcmil380.0 mm²475 A3.35 V (27.89%)8.7 V5.52 V (46.01%)1087.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.51 V (20.92%)9.5 V4.14 V (34.51%)815.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 300 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 300 feet one-way at 12V (DC), you need 7× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (2.99%) and delivers 11.6V at the load.

What size aluminum wire is required for 325 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.14V (34.51%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.