🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 150 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.62%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.07V (17.25%)
Voltage at Load End11.7 VLoss: 0.32 V (102.0 W)
Power & Breaker (125%)3.9 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 150 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A305.75 V (2547.94%)0.0 V504.35 V (4202.91%)99369.6 WDrop/Amp High
12 AWG3.31 mm²20 A192.13 V (1601.12%)0.0 V316.93 V (2641.1%)62443.7 WDrop/Amp High
10 AWG5.26 mm²30 A120.91 V (1007.55%)0.0 V199.44 V (1661.99%)39294.4 WDrop/Amp High
8 AWG8.37 mm²50 A75.98 V (633.18%)0.0 V125.33 V (1044.45%)24694.0 WDrop/Amp High
6 AWG13.3 mm²65 A47.82 V (398.47%)0.0 V78.88 V (657.3%)15540.5 WDrop/Amp High
4 AWG21.15 mm²85 A30.07 V (250.58%)0.0 V49.6 V (413.34%)9772.5 WDrop/Amp High
3 AWG26.67 mm²100 A23.85 V (198.71%)0.0 V39.33 V (327.79%)7749.9 WDrop/Amp High
2 AWG33.62 mm²115 A18.92 V (157.64%)0.0 V31.2 V (260.03%)6147.8 WDrop/Amp High
1 AWG42.41 mm²130 A15.0 V (124.96%)0.0 V24.74 V (206.13%)4873.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.89 V (99.08%)0.1 V19.61 V (163.43%)3864.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.43 V (78.6%)2.6 V15.56 V (129.65%)3065.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.48 V (62.34%)4.5 V12.34 V (102.84%)2431.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.93 V (49.44%)6.1 V9.79 V (81.55%)1928.1 WDrop/Amp High
250 kcmil126.7 mm²255 A5.02 V (41.83%)7.0 V8.28 V (69.0%)1631.3 WDrop/Amp High
300 kcmil152.0 mm²285 A4.18 V (34.87%)7.8 V6.9 V (57.51%)1359.8 WDrop/Amp High
350 kcmil177.3 mm²310 A3.59 V (29.89%)8.4 V5.92 V (49.31%)1165.8 WDrop/Amp High
400 kcmil202.7 mm²335 A3.14 V (26.15%)8.9 V5.18 V (43.13%)1019.7 WDrop/Amp High
500 kcmil253.4 mm²380 A2.51 V (20.91%)9.5 V4.14 V (34.5%)815.7 WDrop/Amp High
600 kcmil304.0 mm²420 A2.09 V (17.43%)9.9 V3.45 V (28.76%)679.9 WDrop/Amp High
750 kcmil380.0 mm²475 A1.67 V (13.95%)10.3 V2.76 V (23.01%)543.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.26 V (10.46%)10.7 V2.07 V (17.25%)407.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 150 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 150 feet one-way at 12V (DC), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.32V (2.62%) and delivers 11.7V at the load.

What size aluminum wire is required for 325 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.07V (17.25%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.