🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.42V (20.13%)
Voltage at Load End11.7 VLoss: 0.29 V (95.2 W)
Power & Breaker (125%)3.9 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A356.71 V (2972.59%)0.0 V588.41 V (4903.39%)115931.2 WDrop/Amp High
12 AWG3.31 mm²20 A224.16 V (1867.97%)0.0 V369.75 V (3081.28%)72851.0 WDrop/Amp High
10 AWG5.26 mm²30 A141.06 V (1175.47%)0.0 V232.68 V (1938.98%)45843.5 WDrop/Amp High
8 AWG8.37 mm²50 A88.65 V (738.71%)0.0 V146.22 V (1218.52%)28809.7 WDrop/Amp High
6 AWG13.3 mm²65 A55.79 V (464.89%)0.0 V92.02 V (766.85%)18130.6 WDrop/Amp High
4 AWG21.15 mm²85 A35.08 V (292.34%)0.0 V57.87 V (482.22%)11401.3 WDrop/Amp High
3 AWG26.67 mm²100 A27.82 V (231.83%)0.0 V45.89 V (382.42%)9041.5 WDrop/Amp High
2 AWG33.62 mm²115 A22.07 V (183.91%)0.0 V36.4 V (303.36%)7172.4 WDrop/Amp High
1 AWG42.41 mm²130 A17.49 V (145.79%)0.0 V28.86 V (240.49%)5685.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.87 V (115.59%)0.0 V22.88 V (190.67%)4508.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.0 V (91.7%)1.0 V18.15 V (151.25%)3576.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.73 V (72.73%)3.3 V14.4 V (119.97%)2836.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.92 V (57.68%)5.1 V11.42 V (95.14%)2249.4 WDrop/Amp High
250 kcmil126.7 mm²255 A5.86 V (48.8%)6.1 V9.66 V (80.5%)1903.2 WDrop/Amp High
300 kcmil152.0 mm²285 A4.88 V (40.68%)7.1 V8.05 V (67.1%)1586.4 WDrop/Amp High
350 kcmil177.3 mm²310 A4.18 V (34.87%)7.8 V6.9 V (57.52%)1360.0 WDrop/Amp High
400 kcmil202.7 mm²335 A3.66 V (30.5%)8.3 V6.04 V (50.32%)1189.6 WDrop/Amp High
500 kcmil253.4 mm²380 A2.93 V (24.4%)9.1 V4.83 V (40.25%)951.6 WDrop/Amp High
600 kcmil304.0 mm²420 A2.44 V (20.34%)9.6 V4.03 V (33.55%)793.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.95 V (16.27%)10.0 V3.22 V (26.84%)634.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.46 V (12.2%)10.5 V2.42 V (20.13%)475.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 175 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.29V (2.44%) and delivers 11.7V at the load.

What size aluminum wire is required for 325 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.42V (20.13%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.