🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 125 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.91%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.73V (14.38%)
Voltage at Load End11.7 VLoss: 0.35 V (113.3 W)
Power & Breaker (125%)3.9 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 125 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A254.79 V (2123.28%)0.0 V420.29 V (3502.42%)82808.0 WDrop/Amp High
12 AWG3.31 mm²20 A160.11 V (1334.27%)0.0 V264.11 V (2200.92%)52036.4 WDrop/Amp High
10 AWG5.26 mm²30 A100.75 V (839.62%)0.0 V166.2 V (1384.99%)32745.4 WDrop/Amp High
8 AWG8.37 mm²50 A63.32 V (527.65%)0.0 V104.44 V (870.37%)20578.3 WDrop/Amp High
6 AWG13.3 mm²65 A39.85 V (332.06%)0.0 V65.73 V (547.75%)12950.4 WDrop/Amp High
4 AWG21.15 mm²85 A25.06 V (208.81%)0.0 V41.33 V (344.45%)8143.8 WDrop/Amp High
3 AWG26.67 mm²100 A19.87 V (165.6%)0.0 V32.78 V (273.15%)6458.2 WDrop/Amp High
2 AWG33.62 mm²115 A15.76 V (131.36%)0.0 V26.0 V (216.69%)5123.2 WDrop/Amp High
1 AWG42.41 mm²130 A12.5 V (104.14%)0.0 V20.61 V (171.78%)4061.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.91 V (82.57%)2.1 V16.34 V (136.19%)3220.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.86 V (65.5%)4.1 V12.96 V (108.04%)2554.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.23 V (51.95%)5.8 V10.28 V (85.7%)2026.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.94 V (41.2%)7.1 V8.15 V (67.96%)1606.7 WDrop/Amp High
250 kcmil126.7 mm²255 A4.18 V (34.86%)7.8 V6.9 V (57.5%)1359.4 WDrop/Amp High
300 kcmil152.0 mm²285 A3.49 V (29.06%)8.5 V5.75 V (47.93%)1133.2 WDrop/Amp High
350 kcmil177.3 mm²310 A2.99 V (24.91%)9.0 V4.93 V (41.09%)971.5 WDrop/Amp High
400 kcmil202.7 mm²335 A2.61 V (21.79%)9.4 V4.31 V (35.94%)849.7 WDrop/Amp High
500 kcmil253.4 mm²380 A2.09 V (17.43%)9.9 V3.45 V (28.75%)679.7 WDrop/Amp High
600 kcmil304.0 mm²420 A1.74 V (14.53%)10.3 V2.88 V (23.96%)566.6 WDrop/Amp High
750 kcmil380.0 mm²475 A1.39 V (11.62%)10.6 V2.3 V (19.17%)453.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.05 V (8.72%)11.0 V1.73 V (14.38%)339.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 125 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 125 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.91%) and delivers 11.7V at the load.

What size aluminum wire is required for 325 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.73V (14.38%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.