🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 20 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.28V (2.3%)
Voltage at Load End11.7 VLoss: 0.33 V (108.8 W)
Power & Breaker (125%)3.9 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 20 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A40.77 V (339.72%)0.0 V67.25 V (560.39%)13249.3 WDrop/Amp High
12 AWG3.31 mm²20 A25.62 V (213.48%)0.0 V42.26 V (352.15%)8325.8 WDrop/Amp High
10 AWG5.26 mm²30 A16.12 V (134.34%)0.0 V26.59 V (221.6%)5239.3 WDrop/Amp High
8 AWG8.37 mm²50 A10.13 V (84.42%)1.9 V16.71 V (139.26%)3292.5 WDrop/Amp High
6 AWG13.3 mm²65 A6.38 V (53.13%)5.6 V10.52 V (87.64%)2072.1 WDrop/Amp High
4 AWG21.15 mm²85 A4.01 V (33.41%)8.0 V6.61 V (55.11%)1303.0 WDrop/Amp High
3 AWG26.67 mm²100 A3.18 V (26.5%)8.8 V5.24 V (43.7%)1033.3 WDrop/Amp High
2 AWG33.62 mm²115 A2.52 V (21.02%)9.5 V4.16 V (34.67%)819.7 WDrop/Amp High
1 AWG42.41 mm²130 A2.0 V (16.66%)10.0 V3.3 V (27.48%)649.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.59 V (13.21%)10.4 V2.61 V (21.79%)515.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.26 V (10.48%)10.7 V2.07 V (17.29%)408.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.0 V (8.31%)11.0 V1.65 V (13.71%)324.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.79 V (6.59%)11.2 V1.3 V (10.87%)257.1 WDrop/Amp High
250 kcmil126.7 mm²255 A0.67 V (5.58%)11.3 V1.1 V (9.2%)217.5 WDrop/Amp High
300 kcmil152.0 mm²285 A0.56 V (4.65%)11.4 V0.92 V (7.67%)181.3 WDrop/Amp High
350 kcmil177.3 mm²310 A0.48 V (3.99%)11.5 V0.79 V (6.57%)155.4 WDrop/Amp High
400 kcmil202.7 mm²335 A0.42 V (3.49%)11.6 V0.69 V (5.75%)136.0 W~ ≤5%
500 kcmil253.4 mm²380 A0.33 V (2.79%)11.7 V0.55 V (4.6%)108.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.28 V (2.32%)11.7 V0.46 V (3.83%)90.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.22 V (1.86%)11.8 V0.37 V (3.07%)72.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.17 V (1.39%)11.8 V0.28 V (2.3%)54.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 20 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 20 feet one-way at 12V (DC), you need 500 kcmil copper wire. This produces a voltage drop of 0.33V (2.79%) and delivers 11.7V at the load.

What size aluminum wire is required for 325 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.28V (2.3%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.