🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 2.83%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 11.95V (2.49%)
Voltage at Load End466.4 VLoss: 13.59 V (7647.6 W)
Power & Breaker (125%)270.2 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1323.95 V (275.82%)0.0 V2183.89 V (454.98%)745271.7 WDrop/Amp High
12 AWG3.31 mm²20 A831.97 V (173.33%)0.0 V1372.36 V (285.91%)468327.8 WDrop/Amp High
10 AWG5.26 mm²30 A523.54 V (109.07%)0.0 V863.59 V (179.92%)294708.2 WDrop/Amp High
8 AWG8.37 mm²50 A329.01 V (68.54%)151.0 V542.71 V (113.07%)185204.9 WDrop/Amp High
6 AWG13.3 mm²65 A207.05 V (43.14%)272.9 V341.54 V (71.15%)116553.8 WDrop/Amp High
4 AWG21.15 mm²85 A130.2 V (27.13%)349.8 V214.78 V (44.74%)73293.9 WDrop/Amp High
3 AWG26.67 mm²100 A103.25 V (21.51%)376.7 V170.32 V (35.48%)58123.9 WDrop/Amp High
2 AWG33.62 mm²115 A81.91 V (17.06%)398.1 V135.11 V (28.15%)46108.4 WDrop/Amp High
1 AWG42.41 mm²130 A64.93 V (13.53%)415.1 V107.11 V (22.31%)36551.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A51.48 V (10.73%)428.5 V84.92 V (17.69%)28980.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A40.84 V (8.51%)439.2 V67.37 V (14.03%)22989.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A32.39 V (6.75%)447.6 V53.43 V (11.13%)18235.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A25.69 V (5.35%)454.3 V42.37 V (8.83%)14460.5 WDrop/Amp High
250 kcmil126.7 mm²255 A21.73 V (4.53%)458.3 V35.85 V (7.47%)12234.9 WDrop/Amp High
300 kcmil152.0 mm²285 A18.12 V (3.77%)461.9 V29.88 V (6.23%)10198.5 WDrop/Amp High
350 kcmil177.3 mm²310 A15.53 V (3.24%)464.5 V25.62 V (5.34%)8743.2 WDrop/Amp High
400 kcmil202.7 mm²335 A13.59 V (2.83%)466.4 V22.41 V (4.67%)7647.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A10.87 V (2.26%)469.1 V17.93 V (3.73%)6117.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A9.06 V (1.89%)470.9 V14.94 V (3.11%)5099.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A7.25 V (1.51%)472.8 V11.95 V (2.49%)4079.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A5.43 V (1.13%)474.6 V8.96 V (1.87%)3059.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 750 feet one-way at 480V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 13.59V (2.83%) and delivers 466.4V at the load.

What size aluminum wire is required for 325 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 11.95V (2.49%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.