🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 175 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)4 AWGDrop: 5.4V (2.59%)
Voltage at Load End202.8 VLoss: 5.2 V (315.4 W)
Power & Breaker (125%)12.61 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 175 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A33.27 V (15.99%)174.7 V54.88 V (26.38%)2016.8 WDrop/Amp High
12 AWG3.31 mm²20 A20.91 V (10.05%)187.1 V34.48 V (16.58%)1267.3 WDrop/Amp High
10 AWG5.26 mm²30 A13.16 V (6.32%)194.8 V21.7 V (10.43%)797.5 WDrop/Amp High
8 AWG8.37 mm²50 A8.27 V (3.97%)199.7 V13.64 V (6.56%)501.2 W~ ≤5%
6 AWG13.3 mm²65 A5.2 V (2.5%)202.8 V8.58 V (4.13%)315.4 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A3.27 V (1.57%)204.7 V5.4 V (2.59%)198.3 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.59 V (1.25%)205.4 V4.28 V (2.06%)157.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.06 V (0.99%)205.9 V3.4 V (1.63%)124.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.63 V (0.78%)206.4 V2.69 V (1.29%)98.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.29 V (0.62%)206.7 V2.13 V (1.03%)78.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.03 V (0.49%)207.0 V1.69 V (0.81%)62.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.81 V (0.39%)207.2 V1.34 V (0.65%)49.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.65 V (0.31%)207.4 V1.06 V (0.51%)39.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.55 V (0.26%)207.5 V0.9 V (0.43%)33.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.46 V (0.22%)207.5 V0.75 V (0.36%)27.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.39 V (0.19%)207.6 V0.64 V (0.31%)23.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.34 V (0.16%)207.7 V0.56 V (0.27%)20.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.27 V (0.13%)207.7 V0.45 V (0.22%)16.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.23 V (0.11%)207.8 V0.38 V (0.18%)13.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.18 V (0.09%)207.8 V0.3 V (0.14%)11.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.07%)207.9 V0.23 V (0.11%)8.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 175 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 175 feet one-way at 208V (3-Phase), you need 6 AWG copper wire. This produces a voltage drop of 5.2V (2.5%) and delivers 202.8V at the load.

What size aluminum wire is required for 35 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 5.4V (2.59%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.