⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 50 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.14%
Aluminum Wire (≤3% Drop)8 AWGDrop: 3.9V (1.87%)
Voltage at Load End205.6 VLoss: 2.36 V (143.2 W)
Power & Breaker (125%)12.61 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 50 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A9.51 V (4.57%)198.5 V15.68 V (7.54%)576.2 WDrop/Amp High
12 AWG3.31 mm²20 A5.97 V (2.87%)202.0 V9.85 V (4.74%)362.1 WDrop/Amp High
10 AWG5.26 mm²30 A3.76 V (1.81%)204.2 V6.2 V (2.98%)227.9 WDrop/Amp High
8 AWG8.37 mm²50 A2.36 V (1.14%)205.6 V3.9 V (1.87%)143.2 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.49 V (0.71%)206.5 V2.45 V (1.18%)90.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.93 V (0.45%)207.1 V1.54 V (0.74%)56.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.74 V (0.36%)207.3 V1.22 V (0.59%)44.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.59 V (0.28%)207.4 V0.97 V (0.47%)35.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.47 V (0.22%)207.5 V0.77 V (0.37%)28.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.37 V (0.18%)207.6 V0.61 V (0.29%)22.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.29 V (0.14%)207.7 V0.48 V (0.23%)17.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.23 V (0.11%)207.8 V0.38 V (0.18%)14.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.18 V (0.09%)207.8 V0.3 V (0.15%)11.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.16 V (0.08%)207.8 V0.26 V (0.12%)9.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.13 V (0.06%)207.9 V0.21 V (0.1%)7.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.11 V (0.05%)207.9 V0.18 V (0.09%)6.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.1 V (0.05%)207.9 V0.16 V (0.08%)5.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.08 V (0.04%)207.9 V0.13 V (0.06%)4.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.07 V (0.03%)207.9 V0.11 V (0.05%)3.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.05 V (0.03%)207.9 V0.09 V (0.04%)3.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.04 V (0.02%)208.0 V0.06 V (0.03%)2.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 50 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 50 feet one-way at 208V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 2.36V (1.14%) and delivers 205.6V at the load.

What size aluminum wire is required for 35 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 8 AWG to maintain voltage drop at 3.9V (1.87%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.