⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 600 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.69%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 5.8V (2.79%)
Voltage at Load End202.4 VLoss: 5.59 V (339.1 W)
Power & Breaker (125%)12.61 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 600 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A114.06 V (54.84%)93.9 V188.15 V (90.46%)6914.7 WDrop/Amp High
12 AWG3.31 mm²20 A71.68 V (34.46%)136.3 V118.23 V (56.84%)4345.2 WDrop/Amp High
10 AWG5.26 mm²30 A45.1 V (21.69%)162.9 V74.4 V (35.77%)2734.3 WDrop/Amp High
8 AWG8.37 mm²50 A28.35 V (13.63%)179.7 V46.76 V (22.48%)1718.4 WDrop/Amp High
6 AWG13.3 mm²65 A17.84 V (8.58%)190.2 V29.43 V (14.15%)1081.4 WDrop/Amp High
4 AWG21.15 mm²85 A11.22 V (5.39%)196.8 V18.5 V (8.9%)680.0 WDrop/Amp High
3 AWG26.67 mm²100 A8.9 V (4.28%)199.1 V14.67 V (7.05%)539.3 W~ ≤5%
2 AWG33.62 mm²115 A7.06 V (3.39%)200.9 V11.64 V (5.6%)427.8 W~ ≤5%
1 AWG42.41 mm²130 A5.59 V (2.69%)202.4 V9.23 V (4.44%)339.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.44 V (2.13%)203.6 V7.32 V (3.52%)268.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.52 V (1.69%)204.5 V5.8 V (2.79%)213.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.79 V (1.34%)205.2 V4.6 V (2.21%)169.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.21 V (1.06%)205.8 V3.65 V (1.76%)134.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.87 V (0.9%)206.1 V3.09 V (1.49%)113.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.56 V (0.75%)206.4 V2.57 V (1.24%)94.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.34 V (0.64%)206.7 V2.21 V (1.06%)81.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.17 V (0.56%)206.8 V1.93 V (0.93%)71.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.94 V (0.45%)207.1 V1.54 V (0.74%)56.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.78 V (0.38%)207.2 V1.29 V (0.62%)47.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.62 V (0.3%)207.4 V1.03 V (0.5%)37.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.47 V (0.23%)207.5 V0.77 V (0.37%)28.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 600 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 600 feet one-way at 208V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 5.59V (2.69%) and delivers 202.4V at the load.

What size aluminum wire is required for 35 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 5.8V (2.79%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.