⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.88%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 14.86V (6.19%)
Voltage at Load End235.5 VLoss: 4.5 V (1577.0 W)
Power & Breaker (125%)84.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2195.15 V (914.64%)0.0 V3620.97 V (1508.74%)768301.2 WDrop/Amp High
12 AWG3.31 mm²20 A1379.43 V (574.76%)0.0 V2275.41 V (948.09%)482799.5 WDrop/Amp High
10 AWG5.26 mm²30 A868.04 V (361.68%)0.0 V1431.86 V (596.61%)303814.9 WDrop/Amp High
8 AWG8.37 mm²50 A545.51 V (227.3%)0.0 V899.83 V (374.93%)190927.9 WDrop/Amp High
6 AWG13.3 mm²65 A343.3 V (143.04%)0.0 V566.29 V (235.95%)120155.4 WDrop/Amp High
4 AWG21.15 mm²85 A215.88 V (89.95%)24.1 V356.1 V (148.38%)75558.7 WDrop/Amp High
3 AWG26.67 mm²100 A171.2 V (71.33%)68.8 V282.4 V (117.67%)59920.0 WDrop/Amp High
2 AWG33.62 mm²115 A135.81 V (56.59%)104.2 V224.02 V (93.34%)47533.2 WDrop/Amp High
1 AWG42.41 mm²130 A107.66 V (44.86%)132.3 V177.59 V (74.0%)37681.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A85.36 V (35.57%)154.6 V140.8 V (58.67%)29876.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A67.71 V (28.21%)172.3 V111.7 V (46.54%)23699.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A53.71 V (22.38%)186.3 V88.6 V (36.92%)18798.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A42.59 V (17.75%)197.4 V70.26 V (29.27%)14907.3 WDrop/Amp High
250 kcmil126.7 mm²255 A36.04 V (15.02%)204.0 V59.44 V (24.77%)12613.0 WDrop/Amp High
300 kcmil152.0 mm²285 A30.04 V (12.52%)210.0 V49.55 V (20.65%)10513.6 WDrop/Amp High
350 kcmil177.3 mm²310 A25.75 V (10.73%)214.2 V42.48 V (17.7%)9013.3 WDrop/Amp High
400 kcmil202.7 mm²335 A22.53 V (9.39%)217.5 V37.16 V (15.48%)7883.9 WDrop/Amp High
500 kcmil253.4 mm²380 A18.02 V (7.51%)222.0 V29.72 V (12.38%)6306.5 WDrop/Amp High
600 kcmil304.0 mm²420 A15.02 V (6.26%)225.0 V24.78 V (10.32%)5256.8 WDrop/Amp High
750 kcmil380.0 mm²475 A12.02 V (5.01%)228.0 V19.82 V (8.26%)4205.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A9.01 V (3.75%)231.0 V14.86 V (6.19%)3153.9 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 1000 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.5V (1.88%) and delivers 235.5V at the load.

What size aluminum wire is required for 350 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 14.86V (6.19%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.