🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 75 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.56%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 1.49V (0.62%)
Voltage at Load End238.6 VLoss: 1.35 V (473.0 W)
Power & Breaker (125%)84.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 75 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A164.64 V (68.6%)75.4 V271.57 V (113.16%)57622.6 WDrop/Amp High
12 AWG3.31 mm²20 A103.46 V (43.11%)136.5 V170.66 V (71.11%)36210.0 WDrop/Amp High
10 AWG5.26 mm²30 A65.1 V (27.13%)174.9 V107.39 V (44.75%)22786.1 WDrop/Amp High
8 AWG8.37 mm²50 A40.91 V (17.05%)199.1 V67.49 V (28.12%)14319.6 WDrop/Amp High
6 AWG13.3 mm²65 A25.75 V (10.73%)214.3 V42.47 V (17.7%)9011.7 WDrop/Amp High
4 AWG21.15 mm²85 A16.19 V (6.75%)223.8 V26.71 V (11.13%)5666.9 WDrop/Amp High
3 AWG26.67 mm²100 A12.84 V (5.35%)227.2 V21.18 V (8.82%)4494.0 WDrop/Amp High
2 AWG33.62 mm²115 A10.19 V (4.24%)229.8 V16.8 V (7.0%)3565.0 WDrop/Amp High
1 AWG42.41 mm²130 A8.07 V (3.36%)231.9 V13.32 V (5.55%)2826.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.4 V (2.67%)233.6 V10.56 V (4.4%)2240.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.08 V (2.12%)234.9 V8.38 V (3.49%)1777.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.03 V (1.68%)236.0 V6.64 V (2.77%)1409.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.19 V (1.33%)236.8 V5.27 V (2.2%)1118.1 WDrop/Amp High
250 kcmil126.7 mm²255 A2.7 V (1.13%)237.3 V4.46 V (1.86%)946.0 WDrop/Amp High
300 kcmil152.0 mm²285 A2.25 V (0.94%)237.7 V3.72 V (1.55%)788.5 WDrop/Amp High
350 kcmil177.3 mm²310 A1.93 V (0.8%)238.1 V3.19 V (1.33%)676.0 WDrop/Amp High
400 kcmil202.7 mm²335 A1.69 V (0.7%)238.3 V2.79 V (1.16%)591.3 WDrop/Amp High
500 kcmil253.4 mm²380 A1.35 V (0.56%)238.6 V2.23 V (0.93%)473.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.13 V (0.47%)238.9 V1.86 V (0.77%)394.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.9 V (0.38%)239.1 V1.49 V (0.62%)315.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.68 V (0.28%)239.3 V1.11 V (0.46%)236.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 75 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 75 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 1.35V (0.56%) and delivers 238.6V at the load.

What size aluminum wire is required for 350 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 1.49V (0.62%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.