🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 20 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 0.15%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 0.4V (0.17%)
Voltage at Load End239.6 VLoss: 0.36 V (126.1 W)
Power & Breaker (125%)84.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A43.9 V (18.29%)196.1 V72.42 V (30.17%)15366.0 WDrop/Amp High
12 AWG3.31 mm²20 A27.59 V (11.5%)212.4 V45.51 V (18.96%)9656.0 WDrop/Amp High
10 AWG5.26 mm²30 A17.36 V (7.23%)222.6 V28.64 V (11.93%)6076.3 WDrop/Amp High
8 AWG8.37 mm²50 A10.91 V (4.55%)229.1 V18.0 V (7.5%)3818.6 WDrop/Amp High
6 AWG13.3 mm²65 A6.87 V (2.86%)233.1 V11.33 V (4.72%)2403.1 WDrop/Amp High
4 AWG21.15 mm²85 A4.32 V (1.8%)235.7 V7.12 V (2.97%)1511.2 WDrop/Amp High
3 AWG26.67 mm²100 A3.42 V (1.43%)236.6 V5.65 V (2.35%)1198.4 WDrop/Amp High
2 AWG33.62 mm²115 A2.72 V (1.13%)237.3 V4.48 V (1.87%)950.7 WDrop/Amp High
1 AWG42.41 mm²130 A2.15 V (0.9%)237.8 V3.55 V (1.48%)753.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A1.71 V (0.71%)238.3 V2.82 V (1.17%)597.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.35 V (0.56%)238.6 V2.23 V (0.93%)474.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.07 V (0.45%)238.9 V1.77 V (0.74%)376.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A0.85 V (0.35%)239.1 V1.41 V (0.59%)298.1 WDrop/Amp High
250 kcmil126.7 mm²255 A0.72 V (0.3%)239.3 V1.19 V (0.5%)252.3 WDrop/Amp High
300 kcmil152.0 mm²285 A0.6 V (0.25%)239.4 V0.99 V (0.41%)210.3 WDrop/Amp High
350 kcmil177.3 mm²310 A0.52 V (0.21%)239.5 V0.85 V (0.35%)180.3 WDrop/Amp High
400 kcmil202.7 mm²335 A0.45 V (0.19%)239.5 V0.74 V (0.31%)157.7 WDrop/Amp High
500 kcmil253.4 mm²380 A0.36 V (0.15%)239.6 V0.59 V (0.25%)126.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.3 V (0.13%)239.7 V0.5 V (0.21%)105.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.24 V (0.1%)239.8 V0.4 V (0.17%)84.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.18 V (0.08%)239.8 V0.3 V (0.12%)63.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 20 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 0.36V (0.15%) and delivers 239.6V at the load.

What size aluminum wire is required for 350 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 0.4V (0.17%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.