🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 450 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.69%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.69V (5.57%)
Voltage at Load End118.0 VLoss: 2.02 V (709.6 W)
Power & Breaker (125%)42.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 450 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A987.82 V (823.18%)0.0 V1629.43 V (1357.86%)345735.5 WDrop/Amp High
12 AWG3.31 mm²20 A620.74 V (517.29%)0.0 V1023.93 V (853.28%)217259.8 WDrop/Amp High
10 AWG5.26 mm²30 A390.62 V (325.52%)0.0 V644.34 V (536.95%)136716.7 WDrop/Amp High
8 AWG8.37 mm²50 A245.48 V (204.57%)0.0 V404.93 V (337.44%)85917.5 WDrop/Amp High
6 AWG13.3 mm²65 A154.49 V (128.74%)0.0 V254.83 V (212.36%)54069.9 WDrop/Amp High
4 AWG21.15 mm²85 A97.15 V (80.96%)22.9 V160.25 V (133.54%)34001.4 WDrop/Amp High
3 AWG26.67 mm²100 A77.04 V (64.2%)43.0 V127.08 V (105.9%)26964.0 WDrop/Amp High
2 AWG33.62 mm²115 A61.11 V (50.93%)58.9 V100.81 V (84.01%)21389.9 WDrop/Amp High
1 AWG42.41 mm²130 A48.45 V (40.37%)71.6 V79.92 V (66.6%)16956.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A38.41 V (32.01%)81.6 V63.36 V (52.8%)13444.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A30.47 V (25.39%)89.5 V50.26 V (41.89%)10664.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A24.17 V (20.14%)95.8 V39.87 V (33.22%)8459.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A19.17 V (15.97%)100.8 V31.62 V (26.35%)6708.3 WDrop/Amp High
250 kcmil126.7 mm²255 A16.22 V (13.51%)103.8 V26.75 V (22.29%)5675.8 WDrop/Amp High
300 kcmil152.0 mm²285 A13.52 V (11.26%)106.5 V22.3 V (18.58%)4731.1 WDrop/Amp High
350 kcmil177.3 mm²310 A11.59 V (9.66%)108.4 V19.12 V (15.93%)4056.0 WDrop/Amp High
400 kcmil202.7 mm²335 A10.14 V (8.45%)109.9 V16.72 V (13.93%)3547.8 WDrop/Amp High
500 kcmil253.4 mm²380 A8.11 V (6.76%)111.9 V13.37 V (11.15%)2837.9 WDrop/Amp High
600 kcmil304.0 mm²420 A6.76 V (5.63%)113.2 V11.15 V (9.29%)2365.6 WDrop/Amp High
750 kcmil380.0 mm²475 A5.41 V (4.51%)114.6 V8.92 V (7.43%)1892.4 W~ ≤5%
1000 kcmil506.7 mm²545 A4.05 V (3.38%)115.9 V6.69 V (5.57%)1419.2 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 450 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 450 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.02V (1.69%) and delivers 118.0V at the load.

What size aluminum wire is required for 350 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.69V (5.57%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.