🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)600 kcmil304.0 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.79V (2.87%)
Voltage at Load End466.1 VLoss: 13.94 V (9051.9 W)
Power & Breaker (125%)311.77 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2036.84 V (424.34%)0.0 V3359.84 V (699.97%)1322967.5 WDrop/Amp High
12 AWG3.31 mm²20 A1279.95 V (266.66%)0.0 V2111.32 V (439.86%)831351.2 WDrop/Amp High
10 AWG5.26 mm²30 A805.44 V (167.8%)0.0 V1328.6 V (276.79%)523150.7 WDrop/Amp High
8 AWG8.37 mm²50 A506.17 V (105.45%)0.0 V834.94 V (173.95%)328766.1 WDrop/Amp High
6 AWG13.3 mm²65 A318.54 V (66.36%)161.5 V525.45 V (109.47%)206900.2 WDrop/Amp High
4 AWG21.15 mm²85 A200.31 V (41.73%)279.7 V330.42 V (68.84%)130107.4 WDrop/Amp High
3 AWG26.67 mm²100 A158.85 V (33.09%)321.1 V262.03 V (54.59%)103178.6 WDrop/Amp High
2 AWG33.62 mm²115 A126.02 V (26.25%)354.0 V207.87 V (43.31%)81849.3 WDrop/Amp High
1 AWG42.41 mm²130 A99.9 V (20.81%)380.1 V164.78 V (34.33%)64885.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A79.2 V (16.5%)400.8 V130.65 V (27.22%)51444.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A62.83 V (13.09%)417.2 V103.64 V (21.59%)40809.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A49.84 V (10.38%)430.2 V82.21 V (17.13%)32370.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A39.52 V (8.23%)440.5 V65.19 V (13.58%)25669.5 WDrop/Amp High
250 kcmil126.7 mm²255 A33.44 V (6.97%)446.6 V55.16 V (11.49%)21718.8 WDrop/Amp High
300 kcmil152.0 mm²285 A27.87 V (5.81%)452.1 V45.98 V (9.58%)18103.8 WDrop/Amp High
350 kcmil177.3 mm²310 A23.9 V (4.98%)456.1 V39.42 V (8.21%)15520.4 WDrop/Amp High
400 kcmil202.7 mm²335 A20.9 V (4.35%)459.1 V34.48 V (7.18%)13575.6 WDrop/Amp High
500 kcmil253.4 mm²380 A16.72 V (3.48%)463.3 V27.58 V (5.75%)10859.4 W~ ≤5%
600 kcmil304.0 mm²420 A13.94 V (2.9%)466.1 V22.99 V (4.79%)9051.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A11.15 V (2.32%)468.9 V18.39 V (3.83%)7241.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A8.36 V (1.74%)471.6 V13.79 V (2.87%)5430.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 1000 feet one-way at 480V (3-Phase), you need 600 kcmil copper wire. This produces a voltage drop of 13.94V (2.9%) and delivers 466.1V at the load.

What size aluminum wire is required for 375 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.79V (2.87%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.