🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 225 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)7× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.59%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.58V (29.86%)
Voltage at Load End11.7 VLoss: 0.31 V (116.4 W)
Power & Breaker (125%)4.5 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 225 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A529.19 V (4409.89%)0.0 V872.91 V (7274.26%)198445.1 WDrop/Amp High
12 AWG3.31 mm²20 A332.54 V (2771.17%)0.0 V548.54 V (4571.14%)124702.7 WDrop/Amp High
10 AWG5.26 mm²30 A209.26 V (1743.84%)0.0 V345.18 V (2876.51%)78472.6 WDrop/Amp High
8 AWG8.37 mm²50 A131.51 V (1095.89%)0.0 V216.92 V (1807.7%)49314.9 WDrop/Amp High
6 AWG13.3 mm²65 A82.76 V (689.67%)0.0 V136.52 V (1137.63%)31035.0 WDrop/Amp High
4 AWG21.15 mm²85 A52.04 V (433.69%)0.0 V85.85 V (715.39%)19516.1 WDrop/Amp High
3 AWG26.67 mm²100 A41.27 V (343.93%)0.0 V68.08 V (567.32%)15476.8 WDrop/Amp High
2 AWG33.62 mm²115 A32.74 V (272.83%)0.0 V54.01 V (450.04%)12277.4 WDrop/Amp High
1 AWG42.41 mm²130 A25.95 V (216.28%)0.0 V42.81 V (356.77%)9732.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.58 V (171.48%)0.0 V33.94 V (282.87%)7716.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.32 V (136.03%)0.0 V26.93 V (224.39%)6121.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.95 V (107.9%)0.0 V21.36 V (177.98%)4855.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.27 V (85.57%)1.7 V16.94 V (141.14%)3850.4 WDrop/Amp High
250 kcmil126.7 mm²255 A8.69 V (72.4%)3.3 V14.33 V (119.42%)3257.8 WDrop/Amp High
300 kcmil152.0 mm²285 A7.24 V (60.35%)4.8 V11.95 V (99.54%)2715.6 WDrop/Amp High
350 kcmil177.3 mm²310 A6.21 V (51.73%)5.8 V10.24 V (85.34%)2328.1 WDrop/Amp High
400 kcmil202.7 mm²335 A5.43 V (45.25%)6.6 V8.96 V (74.64%)2036.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.34 V (36.2%)7.7 V7.17 V (59.71%)1628.9 WDrop/Amp High
600 kcmil304.0 mm²420 A3.62 V (30.17%)8.4 V5.97 V (49.77%)1357.8 WDrop/Amp High
750 kcmil380.0 mm²475 A2.9 V (24.14%)9.1 V4.78 V (39.82%)1086.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.17 V (18.1%)9.8 V3.58 V (29.86%)814.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 225 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 225 feet one-way at 12V (DC), you need 7× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.31V (2.59%) and delivers 11.7V at the load.

What size aluminum wire is required for 375 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.58V (29.86%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.