⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 225 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.81%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 4.14V (1.99%)
Voltage at Load End204.2 VLoss: 3.76 V (2443.4 W)
Power & Breaker (125%)135.1 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 225 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A458.29 V (220.33%)0.0 V755.96 V (363.44%)297667.7 WDrop/Amp High
12 AWG3.31 mm²20 A287.99 V (138.46%)0.0 V475.05 V (228.39%)187054.0 WDrop/Amp High
10 AWG5.26 mm²30 A181.22 V (87.13%)26.8 V298.94 V (143.72%)117708.9 WDrop/Amp High
8 AWG8.37 mm²50 A113.89 V (54.75%)94.1 V187.86 V (90.32%)73972.4 WDrop/Amp High
6 AWG13.3 mm²65 A71.67 V (34.46%)136.3 V118.23 V (56.84%)46552.5 WDrop/Amp High
4 AWG21.15 mm²85 A45.07 V (21.67%)162.9 V74.35 V (35.74%)29274.2 WDrop/Amp High
3 AWG26.67 mm²100 A35.74 V (17.18%)172.3 V58.96 V (28.35%)23215.2 WDrop/Amp High
2 AWG33.62 mm²115 A28.35 V (13.63%)179.6 V46.77 V (22.49%)18416.1 WDrop/Amp High
1 AWG42.41 mm²130 A22.48 V (10.81%)185.5 V37.08 V (17.83%)14599.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.82 V (8.57%)190.2 V29.4 V (14.13%)11575.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.14 V (6.8%)193.9 V23.32 V (11.21%)9182.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.21 V (5.39%)196.8 V18.5 V (8.89%)7283.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.89 V (4.28%)199.1 V14.67 V (7.05%)5775.6 WDrop/Amp High
250 kcmil126.7 mm²255 A7.52 V (3.62%)200.5 V12.41 V (5.97%)4886.7 WDrop/Amp High
300 kcmil152.0 mm²285 A6.27 V (3.02%)201.7 V10.34 V (4.97%)4073.3 WDrop/Amp High
350 kcmil177.3 mm²310 A5.38 V (2.58%)202.6 V8.87 V (4.26%)3492.1 WDrop/Amp High
400 kcmil202.7 mm²335 A4.7 V (2.26%)203.3 V7.76 V (3.73%)3054.5 WDrop/Amp High
500 kcmil253.4 mm²380 A3.76 V (1.81%)204.2 V6.21 V (2.98%)2443.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.14 V (1.51%)204.9 V5.17 V (2.49%)2036.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.51 V (1.21%)205.5 V4.14 V (1.99%)1629.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.88 V (0.9%)206.1 V3.1 V (1.49%)1221.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 225 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 225 feet one-way at 208V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 3.76V (1.81%) and delivers 204.2V at the load.

What size aluminum wire is required for 375 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 4.14V (1.99%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.