🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 225 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.81%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 4.78V (1.99%)
Voltage at Load End235.7 VLoss: 4.34 V (1628.9 W)
Power & Breaker (125%)90.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A529.19 V (220.49%)0.0 V872.91 V (363.71%)198445.1 WDrop/Amp High
12 AWG3.31 mm²20 A332.54 V (138.56%)0.0 V548.54 V (228.56%)124702.7 WDrop/Amp High
10 AWG5.26 mm²30 A209.26 V (87.19%)30.7 V345.18 V (143.83%)78472.6 WDrop/Amp High
8 AWG8.37 mm²50 A131.51 V (54.79%)108.5 V216.92 V (90.39%)49314.9 WDrop/Amp High
6 AWG13.3 mm²65 A82.76 V (34.48%)157.2 V136.52 V (56.88%)31035.0 WDrop/Amp High
4 AWG21.15 mm²85 A52.04 V (21.68%)188.0 V85.85 V (35.77%)19516.1 WDrop/Amp High
3 AWG26.67 mm²100 A41.27 V (17.2%)198.7 V68.08 V (28.37%)15476.8 WDrop/Amp High
2 AWG33.62 mm²115 A32.74 V (13.64%)207.3 V54.01 V (22.5%)12277.4 WDrop/Amp High
1 AWG42.41 mm²130 A25.95 V (10.81%)214.0 V42.81 V (17.84%)9732.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.58 V (8.57%)219.4 V33.94 V (14.14%)7716.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.32 V (6.8%)223.7 V26.93 V (11.22%)6121.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.95 V (5.39%)227.1 V21.36 V (8.9%)4855.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.27 V (4.28%)229.7 V16.94 V (7.06%)3850.4 WDrop/Amp High
250 kcmil126.7 mm²255 A8.69 V (3.62%)231.3 V14.33 V (5.97%)3257.8 WDrop/Amp High
300 kcmil152.0 mm²285 A7.24 V (3.02%)232.8 V11.95 V (4.98%)2715.6 WDrop/Amp High
350 kcmil177.3 mm²310 A6.21 V (2.59%)233.8 V10.24 V (4.27%)2328.1 WDrop/Amp High
400 kcmil202.7 mm²335 A5.43 V (2.26%)234.6 V8.96 V (3.73%)2036.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.34 V (1.81%)235.7 V7.17 V (2.99%)1628.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.62 V (1.51%)236.4 V5.97 V (2.49%)1357.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.9 V (1.21%)237.1 V4.78 V (1.99%)1086.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.17 V (0.91%)237.8 V3.58 V (1.49%)814.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 225 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 4.34V (1.81%) and delivers 235.7V at the load.

What size aluminum wire is required for 375 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 4.78V (1.99%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.