⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 250 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 4.6V (2.21%)
Voltage at Load End203.8 VLoss: 4.18 V (2714.9 W)
Power & Breaker (125%)135.1 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 250 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A509.21 V (244.81%)0.0 V839.96 V (403.83%)330741.9 WDrop/Amp High
12 AWG3.31 mm²20 A319.99 V (153.84%)0.0 V527.83 V (253.76%)207837.8 WDrop/Amp High
10 AWG5.26 mm²30 A201.36 V (96.81%)6.6 V332.15 V (159.69%)130787.7 WDrop/Amp High
8 AWG8.37 mm²50 A126.54 V (60.84%)81.5 V208.74 V (100.35%)82191.5 WDrop/Amp High
6 AWG13.3 mm²65 A79.64 V (38.29%)128.4 V131.36 V (63.15%)51725.0 WDrop/Amp High
4 AWG21.15 mm²85 A50.08 V (24.08%)157.9 V82.61 V (39.71%)32526.9 WDrop/Amp High
3 AWG26.67 mm²100 A39.71 V (19.09%)168.3 V65.51 V (31.49%)25794.6 WDrop/Amp High
2 AWG33.62 mm²115 A31.5 V (15.15%)176.5 V51.97 V (24.98%)20462.3 WDrop/Amp High
1 AWG42.41 mm²130 A24.97 V (12.01%)183.0 V41.2 V (19.81%)16221.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A19.8 V (9.52%)188.2 V32.66 V (15.7%)12861.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.71 V (7.55%)192.3 V25.91 V (12.46%)10202.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.46 V (5.99%)195.5 V20.55 V (9.88%)8092.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.88 V (4.75%)198.1 V16.3 V (7.84%)6417.4 WDrop/Amp High
250 kcmil126.7 mm²255 A8.36 V (4.02%)199.6 V13.79 V (6.63%)5429.7 WDrop/Amp High
300 kcmil152.0 mm²285 A6.97 V (3.35%)201.0 V11.49 V (5.53%)4525.9 WDrop/Amp High
350 kcmil177.3 mm²310 A5.97 V (2.87%)202.0 V9.85 V (4.74%)3880.1 WDrop/Amp High
400 kcmil202.7 mm²335 A5.23 V (2.51%)202.8 V8.62 V (4.14%)3393.9 WDrop/Amp High
500 kcmil253.4 mm²380 A4.18 V (2.01%)203.8 V6.89 V (3.31%)2714.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.48 V (1.68%)204.5 V5.75 V (2.76%)2263.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.79 V (1.34%)205.2 V4.6 V (2.21%)1810.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.09 V (1.0%)205.9 V3.45 V (1.66%)1357.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 250 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 250 feet one-way at 208V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 4.18V (2.01%) and delivers 203.8V at the load.

What size aluminum wire is required for 375 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 4.6V (2.21%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.