⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 250 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.01%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 5.31V (2.21%)
Voltage at Load End235.2 VLoss: 4.83 V (1809.9 W)
Power & Breaker (125%)90.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A587.99 V (244.99%)0.0 V969.9 V (404.13%)220494.6 WDrop/Amp High
12 AWG3.31 mm²20 A369.49 V (153.95%)0.0 V609.48 V (253.95%)138558.5 WDrop/Amp High
10 AWG5.26 mm²30 A232.51 V (96.88%)7.5 V383.54 V (159.81%)87191.8 WDrop/Amp High
8 AWG8.37 mm²50 A146.12 V (60.88%)93.9 V241.03 V (100.43%)54794.4 WDrop/Amp High
6 AWG13.3 mm²65 A91.96 V (38.31%)148.0 V151.68 V (63.2%)34483.4 WDrop/Amp High
4 AWG21.15 mm²85 A57.83 V (24.09%)182.2 V95.39 V (39.74%)21684.6 WDrop/Amp High
3 AWG26.67 mm²100 A45.86 V (19.11%)194.1 V75.64 V (31.52%)17196.4 WDrop/Amp High
2 AWG33.62 mm²115 A36.38 V (15.16%)203.6 V60.01 V (25.0%)13641.5 WDrop/Amp High
1 AWG42.41 mm²130 A28.84 V (12.02%)211.2 V47.57 V (19.82%)10814.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A22.86 V (9.53%)217.1 V37.72 V (15.71%)8574.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A18.14 V (7.56%)221.9 V29.92 V (12.47%)6801.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A14.39 V (5.99%)225.6 V23.73 V (9.89%)5395.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A11.41 V (4.75%)228.6 V18.82 V (7.84%)4278.3 WDrop/Amp High
250 kcmil126.7 mm²255 A9.65 V (4.02%)230.3 V15.92 V (6.63%)3619.8 WDrop/Amp High
300 kcmil152.0 mm²285 A8.05 V (3.35%)232.0 V13.27 V (5.53%)3017.3 WDrop/Amp High
350 kcmil177.3 mm²310 A6.9 V (2.87%)233.1 V11.38 V (4.74%)2586.7 WDrop/Amp High
400 kcmil202.7 mm²335 A6.03 V (2.51%)234.0 V9.95 V (4.15%)2262.6 WDrop/Amp High
500 kcmil253.4 mm²380 A4.83 V (2.01%)235.2 V7.96 V (3.32%)1809.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A4.02 V (1.68%)236.0 V6.64 V (2.77%)1508.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.22 V (1.34%)236.8 V5.31 V (2.21%)1206.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.41 V (1.01%)237.6 V3.98 V (1.66%)905.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 250 feet one-way at 240V (1-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 4.83V (2.01%) and delivers 235.2V at the load.

What size aluminum wire is required for 375 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 5.31V (2.21%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.