🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.42%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.56V (7.96%)
Voltage at Load End117.1 VLoss: 2.9 V (1086.2 W)
Power & Breaker (125%)45.0 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1411.17 V (1175.97%)0.0 V2327.76 V (1939.8%)529187.0 WDrop/Amp High
12 AWG3.31 mm²20 A886.77 V (738.98%)0.0 V1462.76 V (1218.97%)332540.5 WDrop/Amp High
10 AWG5.26 mm²30 A558.03 V (465.02%)0.0 V920.48 V (767.07%)209260.3 WDrop/Amp High
8 AWG8.37 mm²50 A350.68 V (292.24%)0.0 V578.46 V (482.05%)131506.5 WDrop/Amp High
6 AWG13.3 mm²65 A220.69 V (183.91%)0.0 V364.04 V (303.37%)82760.1 WDrop/Amp High
4 AWG21.15 mm²85 A138.78 V (115.65%)0.0 V228.92 V (190.77%)52043.0 WDrop/Amp High
3 AWG26.67 mm²100 A110.06 V (91.71%)9.9 V181.54 V (151.29%)41271.4 WDrop/Amp High
2 AWG33.62 mm²115 A87.31 V (72.75%)32.7 V144.01 V (120.01%)32739.7 WDrop/Amp High
1 AWG42.41 mm²130 A69.21 V (57.68%)50.8 V114.17 V (95.14%)25954.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A54.87 V (45.73%)65.1 V90.52 V (75.43%)20577.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A43.53 V (36.27%)76.5 V71.8 V (59.84%)16323.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A34.53 V (28.77%)85.5 V56.96 V (47.46%)12948.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A27.38 V (22.82%)92.6 V45.17 V (37.64%)10267.8 WDrop/Amp High
250 kcmil126.7 mm²255 A23.17 V (19.31%)96.8 V38.21 V (31.85%)8687.5 WDrop/Amp High
300 kcmil152.0 mm²285 A19.31 V (16.09%)100.7 V31.85 V (26.54%)7241.5 WDrop/Amp High
350 kcmil177.3 mm²310 A16.56 V (13.8%)103.4 V27.31 V (22.76%)6208.2 WDrop/Amp High
400 kcmil202.7 mm²335 A14.48 V (12.07%)105.5 V23.89 V (19.91%)5430.2 WDrop/Amp High
500 kcmil253.4 mm²380 A11.58 V (9.65%)108.4 V19.11 V (15.92%)4343.8 WDrop/Amp High
600 kcmil304.0 mm²420 A9.66 V (8.05%)110.3 V15.93 V (13.27%)3620.8 WDrop/Amp High
750 kcmil380.0 mm²475 A7.72 V (6.44%)112.3 V12.74 V (10.62%)2896.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.79 V (4.83%)114.2 V9.56 V (7.96%)2172.3 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 600 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.9V (2.42%) and delivers 117.1V at the load.

What size aluminum wire is required for 375 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.56V (7.96%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.