🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 20 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.17%
Aluminum Wire (≤3% Drop)6 AWGDrop: 1.46V (1.21%)
Voltage at Load End118.6 VLoss: 1.4 V (63.1 W)
Power & Breaker (125%)5.4 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 20 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A5.64 V (4.7%)114.4 V9.31 V (7.76%)254.0 WDrop/Amp High
12 AWG3.31 mm²20 A3.55 V (2.96%)116.5 V5.85 V (4.88%)159.6 WDrop/Amp High
10 AWG5.26 mm²30 A2.23 V (1.86%)117.8 V3.68 V (3.07%)100.4 WDrop/Amp High
8 AWG8.37 mm²50 A1.4 V (1.17%)118.6 V2.31 V (1.93%)63.1 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.88 V (0.74%)119.1 V1.46 V (1.21%)39.7 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.56 V (0.46%)119.4 V0.92 V (0.76%)25.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.44 V (0.37%)119.6 V0.73 V (0.61%)19.8 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.35 V (0.29%)119.7 V0.58 V (0.48%)15.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.28 V (0.23%)119.7 V0.46 V (0.38%)12.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.22 V (0.18%)119.8 V0.36 V (0.3%)9.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.17 V (0.15%)119.8 V0.29 V (0.24%)7.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.14 V (0.12%)119.9 V0.23 V (0.19%)6.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.11 V (0.09%)119.9 V0.18 V (0.15%)4.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.09 V (0.08%)119.9 V0.15 V (0.13%)4.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.08 V (0.06%)119.9 V0.13 V (0.11%)3.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.07 V (0.06%)119.9 V0.11 V (0.09%)3.0 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.06 V (0.05%)119.9 V0.1 V (0.08%)2.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.05 V (0.04%)120.0 V0.08 V (0.06%)2.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.04 V (0.03%)120.0 V0.06 V (0.05%)1.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.03 V (0.03%)120.0 V0.05 V (0.04%)1.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.02 V (0.02%)120.0 V0.04 V (0.03%)1.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 20 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 20 feet one-way at 120V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 1.4V (1.17%) and delivers 118.6V at the load.

What size aluminum wire is required for 45 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 1.46V (1.21%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.