🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 75 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.76%
Aluminum Wire (≤3% Drop)4 AWGDrop: 3.43V (2.86%)
Voltage at Load End116.7 VLoss: 3.31 V (149.0 W)
Power & Breaker (125%)5.4 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 75 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A21.17 V (17.64%)98.8 V34.92 V (29.1%)952.5 WDrop/Amp High
12 AWG3.31 mm²20 A13.3 V (11.08%)106.7 V21.94 V (18.28%)598.6 WDrop/Amp High
10 AWG5.26 mm²30 A8.37 V (6.98%)111.6 V13.81 V (11.51%)376.7 WDrop/Amp High
8 AWG8.37 mm²50 A5.26 V (4.38%)114.7 V8.68 V (7.23%)236.7 W~ ≤5%
6 AWG13.3 mm²65 A3.31 V (2.76%)116.7 V5.46 V (4.55%)149.0 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.08 V (1.73%)117.9 V3.43 V (2.86%)93.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.65 V (1.38%)118.3 V2.72 V (2.27%)74.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.31 V (1.09%)118.7 V2.16 V (1.8%)58.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.04 V (0.87%)119.0 V1.71 V (1.43%)46.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.82 V (0.69%)119.2 V1.36 V (1.13%)37.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.65 V (0.54%)119.3 V1.08 V (0.9%)29.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.52 V (0.43%)119.5 V0.85 V (0.71%)23.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.41 V (0.34%)119.6 V0.68 V (0.56%)18.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.35 V (0.29%)119.7 V0.57 V (0.48%)15.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.29 V (0.24%)119.7 V0.48 V (0.4%)13.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.25 V (0.21%)119.8 V0.41 V (0.34%)11.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.22 V (0.18%)119.8 V0.36 V (0.3%)9.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.17 V (0.14%)119.8 V0.29 V (0.24%)7.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.14 V (0.12%)119.9 V0.24 V (0.2%)6.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.1%)119.9 V0.19 V (0.16%)5.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.07%)119.9 V0.14 V (0.12%)3.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 75 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 75 feet one-way at 120V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 3.31V (2.76%) and delivers 116.7V at the load.

What size aluminum wire is required for 45 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 4 AWG to maintain voltage drop at 3.43V (2.86%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.