🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 120 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.78%
Aluminum Wire (≤3% Drop)2 AWGDrop: 3.46V (2.88%)
Voltage at Load End116.7 VLoss: 3.33 V (149.9 W)
Power & Breaker (125%)5.4 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 120 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A33.87 V (28.22%)86.1 V55.87 V (46.56%)1524.1 WDrop/Amp High
12 AWG3.31 mm²20 A21.28 V (17.74%)98.7 V35.11 V (29.26%)957.7 WDrop/Amp High
10 AWG5.26 mm²30 A13.39 V (11.16%)106.6 V22.09 V (18.41%)602.7 WDrop/Amp High
8 AWG8.37 mm²50 A8.42 V (7.01%)111.6 V13.88 V (11.57%)378.7 WDrop/Amp High
6 AWG13.3 mm²65 A5.3 V (4.41%)114.7 V8.74 V (7.28%)238.3 W~ ≤5%
4 AWG21.15 mm²85 A3.33 V (2.78%)116.7 V5.49 V (4.58%)149.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.64 V (2.2%)117.4 V4.36 V (3.63%)118.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A2.1 V (1.75%)117.9 V3.46 V (2.88%)94.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.66 V (1.38%)118.3 V2.74 V (2.28%)74.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.32 V (1.1%)118.7 V2.17 V (1.81%)59.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.04 V (0.87%)119.0 V1.72 V (1.44%)47.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.83 V (0.69%)119.2 V1.37 V (1.14%)37.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.66 V (0.55%)119.3 V1.08 V (0.9%)29.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.56 V (0.46%)119.4 V0.92 V (0.76%)25.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.46 V (0.39%)119.5 V0.76 V (0.64%)20.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.4 V (0.33%)119.6 V0.66 V (0.55%)17.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.35 V (0.29%)119.7 V0.57 V (0.48%)15.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.28 V (0.23%)119.7 V0.46 V (0.38%)12.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.23 V (0.19%)119.8 V0.38 V (0.32%)10.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.19 V (0.15%)119.8 V0.31 V (0.25%)8.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.14 V (0.12%)119.9 V0.23 V (0.19%)6.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 120 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 120 feet one-way at 120V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 3.33V (2.78%) and delivers 116.7V at the load.

What size aluminum wire is required for 45 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 3.46V (2.88%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.