45 Amp Wire Size at 80 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)6 AWG13.3 mm² · Drop: 2.94%
Aluminum Wire (≤3% Drop)3 AWGDrop: 2.9V (2.42%)
Voltage at Load End116.5 VLoss: 3.53 V (158.9 W)
Power & Breaker (125%)5.4 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 80 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A22.58 V (18.82%)97.4 V37.24 V (31.04%)1016.0 WDrop/Amp High
12 AWG3.31 mm²20 A14.19 V (11.82%)105.8 V23.4 V (19.5%)638.5 WDrop/Amp High
10 AWG5.26 mm²30 A8.93 V (7.44%)111.1 V14.73 V (12.27%)401.8 WDrop/Amp High
8 AWG8.37 mm²50 A5.61 V (4.68%)114.4 V9.26 V (7.71%)252.5 W~ ≤5%
6 AWG13.3 mm²65 A3.53 V (2.94%)116.5 V5.82 V (4.85%)158.9 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.22 V (1.85%)117.8 V3.66 V (3.05%)99.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.76 V (1.47%)118.2 V2.9 V (2.42%)79.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.4 V (1.16%)118.6 V2.3 V (1.92%)62.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.11 V (0.92%)118.9 V1.83 V (1.52%)49.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.88 V (0.73%)119.1 V1.45 V (1.21%)39.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.7 V (0.58%)119.3 V1.15 V (0.96%)31.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.55 V (0.46%)119.4 V0.91 V (0.76%)24.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.44 V (0.37%)119.6 V0.72 V (0.6%)19.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.37 V (0.31%)119.6 V0.61 V (0.51%)16.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.31 V (0.26%)119.7 V0.51 V (0.42%)13.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.26 V (0.22%)119.7 V0.44 V (0.36%)11.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.23 V (0.19%)119.8 V0.38 V (0.32%)10.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.19 V (0.15%)119.8 V0.31 V (0.25%)8.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.15 V (0.13%)119.8 V0.25 V (0.21%)7.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.1%)119.9 V0.2 V (0.17%)5.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.08%)119.9 V0.15 V (0.13%)4.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 80 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 80 feet one-way at 120V (1-Phase), you need 6 AWG copper wire. This produces a voltage drop of 3.53V (2.94%) and delivers 116.5V at the load.

What size aluminum wire is required for 45 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 2.9V (2.42%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.