🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 100 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.31%
Aluminum Wire (≤3% Drop)2 AWGDrop: 2.88V (2.4%)
Voltage at Load End117.2 VLoss: 2.78 V (124.9 W)
Power & Breaker (125%)5.4 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 100 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A28.22 V (23.52%)91.8 V46.56 V (38.8%)1270.0 WDrop/Amp High
12 AWG3.31 mm²20 A17.74 V (14.78%)102.3 V29.26 V (24.38%)798.1 WDrop/Amp High
10 AWG5.26 mm²30 A11.16 V (9.3%)108.8 V18.41 V (15.34%)502.2 WDrop/Amp High
8 AWG8.37 mm²50 A7.01 V (5.84%)113.0 V11.57 V (9.64%)315.6 WDrop/Amp High
6 AWG13.3 mm²65 A4.41 V (3.68%)115.6 V7.28 V (6.07%)198.6 W~ ≤5%
4 AWG21.15 mm²85 A2.78 V (2.31%)117.2 V4.58 V (3.82%)124.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A2.2 V (1.83%)117.8 V3.63 V (3.03%)99.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.75 V (1.46%)118.3 V2.88 V (2.4%)78.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.38 V (1.15%)118.6 V2.28 V (1.9%)62.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A1.1 V (0.91%)118.9 V1.81 V (1.51%)49.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.87 V (0.73%)119.1 V1.44 V (1.2%)39.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.69 V (0.58%)119.3 V1.14 V (0.95%)31.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.55 V (0.46%)119.5 V0.9 V (0.75%)24.6 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.46 V (0.39%)119.5 V0.76 V (0.64%)20.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.39 V (0.32%)119.6 V0.64 V (0.53%)17.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.33 V (0.28%)119.7 V0.55 V (0.46%)14.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.29 V (0.24%)119.7 V0.48 V (0.4%)13.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.23 V (0.19%)119.8 V0.38 V (0.32%)10.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.19 V (0.16%)119.8 V0.32 V (0.27%)8.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.15 V (0.13%)119.8 V0.25 V (0.21%)7.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.12 V (0.1%)119.9 V0.19 V (0.16%)5.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 100 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 100 feet one-way at 120V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 2.78V (2.31%) and delivers 117.2V at the load.

What size aluminum wire is required for 45 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 2.88V (2.4%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.