🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 500 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.88%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 6.22V (2.99%)
Voltage at Load End202.0 VLoss: 5.99 V (467.2 W)
Power & Breaker (125%)16.21 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 500 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A122.21 V (58.76%)85.8 V201.59 V (96.92%)9525.4 WDrop/Amp High
12 AWG3.31 mm²20 A76.8 V (36.92%)131.2 V126.68 V (60.9%)5985.7 WDrop/Amp High
10 AWG5.26 mm²30 A48.33 V (23.23%)159.7 V79.72 V (38.33%)3766.7 WDrop/Amp High
8 AWG8.37 mm²50 A30.37 V (14.6%)177.6 V50.1 V (24.08%)2367.1 WDrop/Amp High
6 AWG13.3 mm²65 A19.11 V (9.19%)188.9 V31.53 V (15.16%)1489.7 WDrop/Amp High
4 AWG21.15 mm²85 A12.02 V (5.78%)196.0 V19.83 V (9.53%)936.8 WDrop/Amp High
3 AWG26.67 mm²100 A9.53 V (4.58%)198.5 V15.72 V (7.56%)742.9 W~ ≤5%
2 AWG33.62 mm²115 A7.56 V (3.64%)200.4 V12.47 V (6.0%)589.3 W~ ≤5%
1 AWG42.41 mm²130 A5.99 V (2.88%)202.0 V9.89 V (4.75%)467.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.75 V (2.28%)203.2 V7.84 V (3.77%)370.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.77 V (1.81%)204.2 V6.22 V (2.99%)293.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.99 V (1.44%)205.0 V4.93 V (2.37%)233.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.37 V (1.14%)205.6 V3.91 V (1.88%)184.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.01 V (0.96%)206.0 V3.31 V (1.59%)156.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.67 V (0.8%)206.3 V2.76 V (1.33%)130.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.43 V (0.69%)206.6 V2.36 V (1.14%)111.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.25 V (0.6%)206.7 V2.07 V (0.99%)97.7 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.0 V (0.48%)207.0 V1.65 V (0.8%)78.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.84 V (0.4%)207.2 V1.38 V (0.66%)65.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.67 V (0.32%)207.3 V1.1 V (0.53%)52.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.5 V (0.24%)207.5 V0.83 V (0.4%)39.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 500 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 500 feet one-way at 208V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 5.99V (2.88%) and delivers 202.0V at the load.

What size aluminum wire is required for 45 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 6.22V (2.99%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.