🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 800 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.51%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 6.26V (2.61%)
Voltage at Load End234.0 VLoss: 6.03 V (470.1 W)
Power & Breaker (125%)18.71 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A195.54 V (81.47%)44.5 V322.54 V (134.39%)15240.6 WDrop/Amp High
12 AWG3.31 mm²20 A122.88 V (51.2%)117.1 V202.69 V (84.45%)9577.2 WDrop/Amp High
10 AWG5.26 mm²30 A77.32 V (32.22%)162.7 V127.55 V (53.14%)6026.7 WDrop/Amp High
8 AWG8.37 mm²50 A48.59 V (20.25%)191.4 V80.15 V (33.4%)3787.4 WDrop/Amp High
6 AWG13.3 mm²65 A30.58 V (12.74%)209.4 V50.44 V (21.02%)2383.5 WDrop/Amp High
4 AWG21.15 mm²85 A19.23 V (8.01%)220.8 V31.72 V (13.22%)1498.8 WDrop/Amp High
3 AWG26.67 mm²100 A15.25 V (6.35%)224.8 V25.16 V (10.48%)1188.6 WDrop/Amp High
2 AWG33.62 mm²115 A12.1 V (5.04%)227.9 V19.96 V (8.31%)942.9 WDrop/Amp High
1 AWG42.41 mm²130 A9.59 V (4.0%)230.4 V15.82 V (6.59%)747.5 W~ ≤5%
1/0 AWG53.49 mm²150 A7.6 V (3.17%)232.4 V12.54 V (5.23%)592.6 W~ ≤5%
2/0 AWG67.43 mm²175 A6.03 V (2.51%)234.0 V9.95 V (4.15%)470.1 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.78 V (1.99%)235.2 V7.89 V (3.29%)372.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.79 V (1.58%)236.2 V6.26 V (2.61%)295.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.21 V (1.34%)236.8 V5.3 V (2.21%)250.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.68 V (1.11%)237.3 V4.41 V (1.84%)208.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.29 V (0.96%)237.7 V3.78 V (1.58%)178.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.01 V (0.84%)238.0 V3.31 V (1.38%)156.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.61 V (0.67%)238.4 V2.65 V (1.1%)125.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.34 V (0.56%)238.7 V2.21 V (0.92%)104.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.07 V (0.45%)238.9 V1.77 V (0.74%)83.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.8 V (0.33%)239.2 V1.32 V (0.55%)62.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 800 feet one-way at 240V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 6.03V (2.51%) and delivers 234.0V at the load.

What size aluminum wire is required for 45 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 6.26V (2.61%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.