🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 1000 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 16.55V (3.45%)
Voltage at Load End466.6 VLoss: 13.38 V (10427.8 W)
Power & Breaker (125%)374.12 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 1000 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2444.21 V (509.21%)0.0 V4031.8 V (839.96%)1905073.3 WDrop/Amp High
12 AWG3.31 mm²20 A1535.94 V (319.99%)0.0 V2533.58 V (527.83%)1197145.7 WDrop/Amp High
10 AWG5.26 mm²30 A966.53 V (201.36%)0.0 V1594.33 V (332.15%)753337.0 WDrop/Amp High
8 AWG8.37 mm²50 A607.4 V (126.54%)0.0 V1001.93 V (208.74%)473423.2 WDrop/Amp High
6 AWG13.3 mm²65 A382.25 V (79.64%)97.7 V630.54 V (131.36%)297936.3 WDrop/Amp High
4 AWG21.15 mm²85 A240.38 V (50.08%)239.6 V396.51 V (82.61%)187354.7 WDrop/Amp High
3 AWG26.67 mm²100 A190.62 V (39.71%)289.4 V314.44 V (65.51%)148577.1 WDrop/Amp High
2 AWG33.62 mm²115 A151.22 V (31.5%)328.8 V249.44 V (51.97%)117863.0 WDrop/Amp High
1 AWG42.41 mm²130 A119.88 V (24.97%)360.1 V197.74 V (41.2%)93434.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A95.05 V (19.8%)385.0 V156.78 V (32.66%)74080.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A75.4 V (15.71%)404.6 V124.37 V (25.91%)58765.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A59.8 V (12.46%)420.2 V98.65 V (20.55%)46612.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A47.42 V (9.88%)432.6 V78.23 V (16.3%)36964.1 WDrop/Amp High
250 kcmil126.7 mm²255 A40.13 V (8.36%)439.9 V66.19 V (13.79%)31275.1 WDrop/Amp High
300 kcmil152.0 mm²285 A33.45 V (6.97%)446.6 V55.17 V (11.49%)26069.4 WDrop/Amp High
350 kcmil177.3 mm²310 A28.67 V (5.97%)451.3 V47.3 V (9.85%)22349.4 WDrop/Amp High
400 kcmil202.7 mm²335 A25.08 V (5.23%)454.9 V41.37 V (8.62%)19548.9 WDrop/Amp High
500 kcmil253.4 mm²380 A20.06 V (4.18%)459.9 V33.09 V (6.89%)15637.5 WDrop/Amp High
600 kcmil304.0 mm²420 A16.72 V (3.48%)463.3 V27.59 V (5.75%)13034.7 WDrop/Amp High
750 kcmil380.0 mm²475 A13.38 V (2.79%)466.6 V22.07 V (4.6%)10427.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A10.03 V (2.09%)470.0 V16.55 V (3.45%)7820.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 1000 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 1000 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 13.38V (2.79%) and delivers 466.6V at the load.

What size aluminum wire is required for 450 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 16.55V (3.45%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.