🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

450 Amp Wire Size at 800 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 450 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.93%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.24V (6.37%)
Voltage at Load End204.0 VLoss: 4.01 V (3128.2 W)
Power & Breaker (125%)162.12 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 450 Amps at 800 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1955.37 V (940.08%)0.0 V3225.44 V (1550.69%)1524058.6 WDrop/Amp High
12 AWG3.31 mm²20 A1228.75 V (590.75%)0.0 V2026.86 V (974.45%)957716.6 WDrop/Amp High
10 AWG5.26 mm²30 A773.23 V (371.74%)0.0 V1275.46 V (613.2%)602669.6 WDrop/Amp High
8 AWG8.37 mm²50 A485.92 V (233.62%)0.0 V801.54 V (385.36%)378738.6 WDrop/Amp High
6 AWG13.3 mm²65 A305.8 V (147.02%)0.0 V504.43 V (242.51%)238349.0 WDrop/Amp High
4 AWG21.15 mm²85 A192.3 V (92.45%)15.7 V317.21 V (152.5%)149883.8 WDrop/Amp High
3 AWG26.67 mm²100 A152.5 V (73.32%)55.5 V251.55 V (120.94%)118861.7 WDrop/Amp High
2 AWG33.62 mm²115 A120.97 V (58.16%)87.0 V199.55 V (95.94%)94290.4 WDrop/Amp High
1 AWG42.41 mm²130 A95.9 V (46.11%)112.1 V158.19 V (76.05%)74747.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A76.04 V (36.56%)132.0 V125.42 V (60.3%)59264.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A60.32 V (29.0%)147.7 V99.49 V (47.83%)47012.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A47.84 V (23.0%)160.2 V78.92 V (37.94%)37290.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A37.94 V (18.24%)170.1 V62.58 V (30.09%)29571.3 WDrop/Amp High
250 kcmil126.7 mm²255 A32.1 V (15.43%)175.9 V52.95 V (25.46%)25020.1 WDrop/Amp High
300 kcmil152.0 mm²285 A26.76 V (12.86%)181.2 V44.14 V (21.22%)20855.5 WDrop/Amp High
350 kcmil177.3 mm²310 A22.94 V (11.03%)185.1 V37.84 V (18.19%)17879.5 WDrop/Amp High
400 kcmil202.7 mm²335 A20.06 V (9.65%)187.9 V33.1 V (15.91%)15639.1 WDrop/Amp High
500 kcmil253.4 mm²380 A16.05 V (7.72%)191.9 V26.48 V (12.73%)12510.0 WDrop/Amp High
600 kcmil304.0 mm²420 A13.38 V (6.43%)194.6 V22.07 V (10.61%)10427.8 WDrop/Amp High
750 kcmil380.0 mm²475 A10.7 V (5.15%)197.3 V17.66 V (8.49%)8342.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.03 V (3.86%)200.0 V13.24 V (6.37%)6256.3 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 450 amps at 800 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 450A load over 800 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.01V (1.93%) and delivers 204.0V at the load.

What size aluminum wire is required for 450 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.24V (6.37%).

What breaker size is needed for a 450A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (450A × 1.25 = 562.5A), which corresponds to a standard 600A circuit breaker.