⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 100 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.02V (0.84%)
Voltage at Load End238.4 VLoss: 1.63 V (774.6 W)
Power & Breaker (125%)114.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 100 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A297.91 V (124.13%)0.0 V491.42 V (204.76%)141508.5 WDrop/Amp High
12 AWG3.31 mm²20 A187.21 V (78.0%)52.8 V308.81 V (128.67%)88923.8 WDrop/Amp High
10 AWG5.26 mm²30 A117.81 V (49.09%)122.2 V194.32 V (80.97%)55957.7 WDrop/Amp High
8 AWG8.37 mm²50 A74.03 V (30.85%)166.0 V122.12 V (50.88%)35165.8 WDrop/Amp High
6 AWG13.3 mm²65 A46.59 V (19.41%)193.4 V76.85 V (32.02%)22130.7 WDrop/Amp High
4 AWG21.15 mm²85 A29.3 V (12.21%)210.7 V48.33 V (20.14%)13916.7 WDrop/Amp High
3 AWG26.67 mm²100 A23.23 V (9.68%)216.8 V38.33 V (15.97%)11036.3 WDrop/Amp High
2 AWG33.62 mm²115 A18.43 V (7.68%)221.6 V30.4 V (12.67%)8754.8 WDrop/Amp High
1 AWG42.41 mm²130 A14.61 V (6.09%)225.4 V24.1 V (10.04%)6940.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.58 V (4.83%)228.4 V19.11 V (7.96%)5502.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.19 V (3.83%)230.8 V15.16 V (6.32%)4365.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.29 V (3.04%)232.7 V12.02 V (5.01%)3462.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.78 V (2.41%)234.2 V9.53 V (3.97%)2745.7 WDrop/Amp High
250 kcmil126.7 mm²255 A4.89 V (2.04%)235.1 V8.07 V (3.36%)2323.1 WDrop/Amp High
300 kcmil152.0 mm²285 A4.08 V (1.7%)235.9 V6.72 V (2.8%)1936.4 WDrop/Amp High
350 kcmil177.3 mm²310 A3.49 V (1.46%)236.5 V5.77 V (2.4%)1660.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.06 V (1.27%)236.9 V5.04 V (2.1%)1452.1 WDrop/Amp High
500 kcmil253.4 mm²380 A2.45 V (1.02%)237.6 V4.03 V (1.68%)1161.6 WDrop/Amp High
600 kcmil304.0 mm²420 A2.04 V (0.85%)238.0 V3.36 V (1.4%)968.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.63 V (0.68%)238.4 V2.69 V (1.12%)774.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.22 V (0.51%)238.8 V2.02 V (0.84%)580.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 100 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 100 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.63V (0.68%) and delivers 238.4V at the load.

What size aluminum wire is required for 475 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.02V (0.84%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.