⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.85%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.52V (1.05%)
Voltage at Load End238.0 VLoss: 2.04 V (968.2 W)
Power & Breaker (125%)114.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A372.39 V (155.16%)0.0 V614.27 V (255.95%)176885.7 WDrop/Amp High
12 AWG3.31 mm²20 A234.01 V (97.5%)6.0 V386.01 V (160.84%)111154.7 WDrop/Amp High
10 AWG5.26 mm²30 A147.26 V (61.36%)92.7 V242.91 V (101.21%)69947.2 WDrop/Amp High
8 AWG8.37 mm²50 A92.54 V (38.56%)147.5 V152.65 V (63.6%)43957.2 WDrop/Amp High
6 AWG13.3 mm²65 A58.24 V (24.27%)181.8 V96.07 V (40.03%)27663.3 WDrop/Amp High
4 AWG21.15 mm²85 A36.62 V (15.26%)203.4 V60.41 V (25.17%)17395.8 WDrop/Amp High
3 AWG26.67 mm²100 A29.04 V (12.1%)211.0 V47.91 V (19.96%)13795.4 WDrop/Amp High
2 AWG33.62 mm²115 A23.04 V (9.6%)217.0 V38.0 V (15.83%)10943.6 WDrop/Amp High
1 AWG42.41 mm²130 A18.26 V (7.61%)221.7 V30.13 V (12.55%)8675.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.48 V (6.03%)225.5 V23.89 V (9.95%)6878.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.49 V (4.79%)228.5 V18.95 V (7.9%)5456.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.11 V (3.8%)230.9 V15.03 V (6.26%)4328.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.23 V (3.01%)232.8 V11.92 V (4.97%)3432.1 WDrop/Amp High
250 kcmil126.7 mm²255 A6.11 V (2.55%)233.9 V10.08 V (4.2%)2903.9 WDrop/Amp High
300 kcmil152.0 mm²285 A5.1 V (2.12%)234.9 V8.41 V (3.5%)2420.5 WDrop/Amp High
350 kcmil177.3 mm²310 A4.37 V (1.82%)235.6 V7.21 V (3.0%)2075.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.82 V (1.59%)236.2 V6.3 V (2.63%)1815.1 WDrop/Amp High
500 kcmil253.4 mm²380 A3.06 V (1.27%)236.9 V5.04 V (2.1%)1451.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.55 V (1.06%)237.5 V4.2 V (1.75%)1210.3 WDrop/Amp High
750 kcmil380.0 mm²475 A2.04 V (0.85%)238.0 V3.36 V (1.4%)968.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.53 V (0.64%)238.5 V2.52 V (1.05%)726.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 125 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.04V (0.85%) and delivers 238.0V at the load.

What size aluminum wire is required for 475 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.52V (1.05%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.