⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 80 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.54%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.61V (0.67%)
Voltage at Load End238.7 VLoss: 1.3 V (619.7 W)
Power & Breaker (125%)114.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A238.33 V (99.3%)1.7 V393.13 V (163.81%)113206.8 WDrop/Amp High
12 AWG3.31 mm²20 A149.77 V (62.4%)90.2 V247.04 V (102.94%)71139.0 WDrop/Amp High
10 AWG5.26 mm²30 A94.24 V (39.27%)145.8 V155.46 V (64.77%)44766.2 WDrop/Amp High
8 AWG8.37 mm²50 A59.23 V (24.68%)180.8 V97.7 V (40.71%)28132.6 WDrop/Amp High
6 AWG13.3 mm²65 A37.27 V (15.53%)202.7 V61.48 V (25.62%)17704.5 WDrop/Amp High
4 AWG21.15 mm²85 A23.44 V (9.77%)216.6 V38.66 V (16.11%)11133.3 WDrop/Amp High
3 AWG26.67 mm²100 A18.59 V (7.74%)221.4 V30.66 V (12.78%)8829.0 WDrop/Amp High
2 AWG33.62 mm²115 A14.74 V (6.14%)225.3 V24.32 V (10.13%)7003.9 WDrop/Amp High
1 AWG42.41 mm²130 A11.69 V (4.87%)228.3 V19.28 V (8.03%)5552.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.27 V (3.86%)230.7 V15.29 V (6.37%)4402.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.35 V (3.06%)232.6 V12.13 V (5.05%)3492.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.83 V (2.43%)234.2 V9.62 V (4.01%)2769.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.62 V (1.93%)235.4 V7.63 V (3.18%)2196.6 WDrop/Amp High
250 kcmil126.7 mm²255 A3.91 V (1.63%)236.1 V6.45 V (2.69%)1858.5 WDrop/Amp High
300 kcmil152.0 mm²285 A3.26 V (1.36%)236.7 V5.38 V (2.24%)1549.1 WDrop/Amp High
350 kcmil177.3 mm²310 A2.8 V (1.16%)237.2 V4.61 V (1.92%)1328.1 WDrop/Amp High
400 kcmil202.7 mm²335 A2.45 V (1.02%)237.6 V4.03 V (1.68%)1161.7 WDrop/Amp High
500 kcmil253.4 mm²380 A1.96 V (0.82%)238.0 V3.23 V (1.34%)929.2 WDrop/Amp High
600 kcmil304.0 mm²420 A1.63 V (0.68%)238.4 V2.69 V (1.12%)774.6 WDrop/Amp High
750 kcmil380.0 mm²475 A1.3 V (0.54%)238.7 V2.15 V (0.9%)619.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.98 V (0.41%)239.0 V1.61 V (0.67%)464.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 80 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.3V (0.54%) and delivers 238.7V at the load.

What size aluminum wire is required for 475 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.61V (0.67%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.