🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 20 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.14%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.4V (0.17%)
Voltage at Load End239.7 VLoss: 0.33 V (154.9 W)
Power & Breaker (125%)114.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 20 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A59.58 V (24.83%)180.4 V98.28 V (40.95%)28301.7 WDrop/Amp High
12 AWG3.31 mm²20 A37.44 V (15.6%)202.6 V61.76 V (25.73%)17784.8 WDrop/Amp High
10 AWG5.26 mm²30 A23.56 V (9.82%)216.4 V38.86 V (16.19%)11191.5 WDrop/Amp High
8 AWG8.37 mm²50 A14.81 V (6.17%)225.2 V24.42 V (10.18%)7033.2 WDrop/Amp High
6 AWG13.3 mm²65 A9.32 V (3.88%)230.7 V15.37 V (6.4%)4426.1 WDrop/Amp High
4 AWG21.15 mm²85 A5.86 V (2.44%)234.1 V9.67 V (4.03%)2783.3 WDrop/Amp High
3 AWG26.67 mm²100 A4.65 V (1.94%)235.4 V7.67 V (3.19%)2207.3 WDrop/Amp High
2 AWG33.62 mm²115 A3.69 V (1.54%)236.3 V6.08 V (2.53%)1751.0 WDrop/Amp High
1 AWG42.41 mm²130 A2.92 V (1.22%)237.1 V4.82 V (2.01%)1388.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.32 V (0.97%)237.7 V3.82 V (1.59%)1100.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.84 V (0.77%)238.2 V3.03 V (1.26%)873.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.46 V (0.61%)238.5 V2.4 V (1.0%)692.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.16 V (0.48%)238.8 V1.91 V (0.79%)549.1 WDrop/Amp High
250 kcmil126.7 mm²255 A0.98 V (0.41%)239.0 V1.61 V (0.67%)464.6 WDrop/Amp High
300 kcmil152.0 mm²285 A0.82 V (0.34%)239.2 V1.34 V (0.56%)387.3 WDrop/Amp High
350 kcmil177.3 mm²310 A0.7 V (0.29%)239.3 V1.15 V (0.48%)332.0 WDrop/Amp High
400 kcmil202.7 mm²335 A0.61 V (0.25%)239.4 V1.01 V (0.42%)290.4 WDrop/Amp High
500 kcmil253.4 mm²380 A0.49 V (0.2%)239.5 V0.81 V (0.34%)232.3 WDrop/Amp High
600 kcmil304.0 mm²420 A0.41 V (0.17%)239.6 V0.67 V (0.28%)193.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.33 V (0.14%)239.7 V0.54 V (0.22%)154.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.24 V (0.1%)239.8 V0.4 V (0.17%)116.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 20 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 20 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.33V (0.14%) and delivers 239.7V at the load.

What size aluminum wire is required for 475 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.4V (0.17%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.