⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 40 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.27%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.81V (0.34%)
Voltage at Load End239.3 VLoss: 0.65 V (309.8 W)
Power & Breaker (125%)114.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A119.17 V (49.65%)120.8 V196.57 V (81.9%)56603.4 WDrop/Amp High
12 AWG3.31 mm²20 A74.88 V (31.2%)165.1 V123.52 V (51.47%)35569.5 WDrop/Amp High
10 AWG5.26 mm²30 A47.12 V (19.63%)192.9 V77.73 V (32.39%)22383.1 WDrop/Amp High
8 AWG8.37 mm²50 A29.61 V (12.34%)210.4 V48.85 V (20.35%)14066.3 WDrop/Amp High
6 AWG13.3 mm²65 A18.64 V (7.77%)221.4 V30.74 V (12.81%)8852.3 WDrop/Amp High
4 AWG21.15 mm²85 A11.72 V (4.88%)228.3 V19.33 V (8.05%)5566.7 WDrop/Amp High
3 AWG26.67 mm²100 A9.29 V (3.87%)230.7 V15.33 V (6.39%)4414.5 WDrop/Amp High
2 AWG33.62 mm²115 A7.37 V (3.07%)232.6 V12.16 V (5.07%)3501.9 WDrop/Amp High
1 AWG42.41 mm²130 A5.84 V (2.44%)234.2 V9.64 V (4.02%)2776.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.63 V (1.93%)235.4 V7.64 V (3.18%)2201.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.68 V (1.53%)236.3 V6.06 V (2.53%)1746.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.92 V (1.21%)237.1 V4.81 V (2.0%)1385.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.31 V (0.96%)237.7 V3.81 V (1.59%)1098.3 WDrop/Amp High
250 kcmil126.7 mm²255 A1.96 V (0.82%)238.0 V3.23 V (1.34%)929.2 WDrop/Amp High
300 kcmil152.0 mm²285 A1.63 V (0.68%)238.4 V2.69 V (1.12%)774.6 WDrop/Amp High
350 kcmil177.3 mm²310 A1.4 V (0.58%)238.6 V2.31 V (0.96%)664.0 WDrop/Amp High
400 kcmil202.7 mm²335 A1.22 V (0.51%)238.8 V2.02 V (0.84%)580.8 WDrop/Amp High
500 kcmil253.4 mm²380 A0.98 V (0.41%)239.0 V1.61 V (0.67%)464.6 WDrop/Amp High
600 kcmil304.0 mm²420 A0.82 V (0.34%)239.2 V1.34 V (0.56%)387.3 WDrop/Amp High
750 kcmil380.0 mm²475 A0.65 V (0.27%)239.3 V1.08 V (0.45%)309.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.49 V (0.2%)239.5 V0.81 V (0.34%)232.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 40 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.65V (0.27%) and delivers 239.3V at the load.

What size aluminum wire is required for 475 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.81V (0.34%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.