🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 120 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.42V (1.01%)
Voltage at Load End238.0 VLoss: 1.96 V (929.5 W)
Power & Breaker (125%)114.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A357.5 V (148.96%)0.0 V589.7 V (245.71%)169810.2 WDrop/Amp High
12 AWG3.31 mm²20 A224.65 V (93.6%)15.4 V370.57 V (154.4%)106708.5 WDrop/Amp High
10 AWG5.26 mm²30 A141.37 V (58.9%)98.6 V233.19 V (97.16%)67149.3 WDrop/Amp High
8 AWG8.37 mm²50 A88.84 V (37.02%)151.2 V146.54 V (61.06%)42199.0 WDrop/Amp High
6 AWG13.3 mm²65 A55.91 V (23.3%)184.1 V92.22 V (38.43%)26556.8 WDrop/Amp High
4 AWG21.15 mm²85 A35.16 V (14.65%)204.8 V57.99 V (24.16%)16700.0 WDrop/Amp High
3 AWG26.67 mm²100 A27.88 V (11.62%)212.1 V45.99 V (19.16%)13243.5 WDrop/Amp High
2 AWG33.62 mm²115 A22.12 V (9.22%)217.9 V36.48 V (15.2%)10505.8 WDrop/Amp High
1 AWG42.41 mm²130 A17.53 V (7.31%)222.5 V28.92 V (12.05%)8328.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.9 V (5.79%)226.1 V22.93 V (9.55%)6603.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.03 V (4.59%)229.0 V18.19 V (7.58%)5238.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.75 V (3.64%)231.3 V14.43 V (6.01%)4154.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.94 V (2.89%)233.1 V11.44 V (4.77%)3294.8 WDrop/Amp High
250 kcmil126.7 mm²255 A5.87 V (2.45%)234.1 V9.68 V (4.03%)2787.7 WDrop/Amp High
300 kcmil152.0 mm²285 A4.89 V (2.04%)235.1 V8.07 V (3.36%)2323.7 WDrop/Amp High
350 kcmil177.3 mm²310 A4.19 V (1.75%)235.8 V6.92 V (2.88%)1992.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.67 V (1.53%)236.3 V6.05 V (2.52%)1742.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.93 V (1.22%)237.1 V4.84 V (2.02%)1393.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.45 V (1.02%)237.6 V4.03 V (1.68%)1161.9 WDrop/Amp High
750 kcmil380.0 mm²475 A1.96 V (0.82%)238.0 V3.23 V (1.34%)929.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.47 V (0.61%)238.5 V2.42 V (1.01%)697.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 120 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.96V (0.82%) and delivers 238.0V at the load.

What size aluminum wire is required for 475 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.42V (1.01%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.