🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 200 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.18%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.49V (1.46%)
Voltage at Load End237.2 VLoss: 2.82 V (2323.7 W)
Power & Breaker (125%)197.45 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 200 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A516.0 V (215.0%)0.0 V851.16 V (354.65%)424525.6 WDrop/Amp High
12 AWG3.31 mm²20 A324.25 V (135.11%)0.0 V534.87 V (222.86%)266771.4 WDrop/Amp High
10 AWG5.26 mm²30 A204.05 V (85.02%)36.0 V336.58 V (140.24%)167873.2 WDrop/Amp High
8 AWG8.37 mm²50 A128.23 V (53.43%)111.8 V211.52 V (88.13%)105497.4 WDrop/Amp High
6 AWG13.3 mm²65 A80.7 V (33.62%)159.3 V133.11 V (55.46%)66392.0 WDrop/Amp High
4 AWG21.15 mm²85 A50.75 V (21.14%)189.3 V83.71 V (34.88%)41750.0 WDrop/Amp High
3 AWG26.67 mm²100 A40.24 V (16.77%)199.8 V66.38 V (27.66%)33108.9 WDrop/Amp High
2 AWG33.62 mm²115 A31.92 V (13.3%)208.1 V52.66 V (21.94%)26264.5 WDrop/Amp High
1 AWG42.41 mm²130 A25.31 V (10.54%)214.7 V41.75 V (17.39%)20820.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.07 V (8.36%)219.9 V33.1 V (13.79%)16508.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.92 V (6.63%)224.1 V26.26 V (10.94%)13095.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.63 V (5.26%)227.4 V20.83 V (8.68%)10387.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.01 V (4.17%)230.0 V16.52 V (6.88%)8237.1 WDrop/Amp High
250 kcmil126.7 mm²255 A8.47 V (3.53%)231.5 V13.97 V (5.82%)6969.3 WDrop/Amp High
300 kcmil152.0 mm²285 A7.06 V (2.94%)232.9 V11.65 V (4.85%)5809.3 WDrop/Amp High
350 kcmil177.3 mm²310 A6.05 V (2.52%)233.9 V9.99 V (4.16%)4980.3 WDrop/Amp High
400 kcmil202.7 mm²335 A5.29 V (2.21%)234.7 V8.73 V (3.64%)4356.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.24 V (1.76%)235.8 V6.99 V (2.91%)3484.7 WDrop/Amp High
600 kcmil304.0 mm²420 A3.53 V (1.47%)236.5 V5.82 V (2.43%)2904.6 WDrop/Amp High
750 kcmil380.0 mm²475 A2.82 V (1.18%)237.2 V4.66 V (1.94%)2323.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.12 V (0.88%)237.9 V3.49 V (1.46%)1742.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 200 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 200 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.82V (1.18%) and delivers 237.2V at the load.

What size aluminum wire is required for 475 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.49V (1.46%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.