🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 300 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.88%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.24V (1.09%)
Voltage at Load End475.8 VLoss: 4.24 V (3485.6 W)
Power & Breaker (125%)394.91 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 300 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A774.0 V (161.25%)0.0 V1276.74 V (265.99%)636788.4 WDrop/Amp High
12 AWG3.31 mm²20 A486.38 V (101.33%)0.0 V802.3 V (167.15%)400157.0 WDrop/Amp High
10 AWG5.26 mm²30 A306.07 V (63.76%)173.9 V504.87 V (105.18%)251809.9 WDrop/Amp High
8 AWG8.37 mm²50 A192.34 V (40.07%)287.7 V317.28 V (66.1%)158246.1 WDrop/Amp High
6 AWG13.3 mm²65 A121.05 V (25.22%)359.0 V199.67 V (41.6%)99588.0 WDrop/Amp High
4 AWG21.15 mm²85 A76.12 V (15.86%)403.9 V125.56 V (26.16%)62625.1 WDrop/Amp High
3 AWG26.67 mm²100 A60.36 V (12.58%)419.6 V99.57 V (20.74%)49663.3 WDrop/Amp High
2 AWG33.62 mm²115 A47.89 V (9.98%)432.1 V78.99 V (16.46%)39396.8 WDrop/Amp High
1 AWG42.41 mm²130 A37.96 V (7.91%)442.0 V62.62 V (13.05%)31231.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A30.1 V (6.27%)449.9 V49.65 V (10.34%)24762.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A23.88 V (4.97%)456.1 V39.38 V (8.2%)19642.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A18.94 V (3.95%)461.1 V31.24 V (6.51%)15580.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.02 V (3.13%)465.0 V24.77 V (5.16%)12355.6 WDrop/Amp High
250 kcmil126.7 mm²255 A12.71 V (2.65%)467.3 V20.96 V (4.37%)10454.0 WDrop/Amp High
300 kcmil152.0 mm²285 A10.59 V (2.21%)469.4 V17.47 V (3.64%)8713.9 WDrop/Amp High
350 kcmil177.3 mm²310 A9.08 V (1.89%)470.9 V14.98 V (3.12%)7470.5 WDrop/Amp High
400 kcmil202.7 mm²335 A7.94 V (1.65%)472.1 V13.1 V (2.73%)6534.4 WDrop/Amp High
500 kcmil253.4 mm²380 A6.35 V (1.32%)473.6 V10.48 V (2.18%)5227.0 WDrop/Amp High
600 kcmil304.0 mm²420 A5.3 V (1.1%)474.7 V8.74 V (1.82%)4357.0 WDrop/Amp High
750 kcmil380.0 mm²475 A4.24 V (0.88%)475.8 V6.99 V (1.46%)3485.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.18 V (0.66%)476.8 V5.24 V (1.09%)2614.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 300 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 300 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 4.24V (0.88%) and delivers 475.8V at the load.

What size aluminum wire is required for 475 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.24V (1.09%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.