🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.38%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.11V (2.94%)
Voltage at Load End203.1 VLoss: 4.94 V (4066.5 W)
Power & Breaker (125%)171.13 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A903.0 V (434.13%)0.0 V1489.53 V (716.12%)742919.8 WDrop/Amp High
12 AWG3.31 mm²20 A567.44 V (272.81%)0.0 V936.02 V (450.01%)466849.9 WDrop/Amp High
10 AWG5.26 mm²30 A357.08 V (171.67%)0.0 V589.01 V (283.18%)293778.2 WDrop/Amp High
8 AWG8.37 mm²50 A224.4 V (107.89%)0.0 V370.16 V (177.96%)184620.4 WDrop/Amp High
6 AWG13.3 mm²65 A141.22 V (67.89%)66.8 V232.95 V (111.99%)116185.9 WDrop/Amp High
4 AWG21.15 mm²85 A88.81 V (42.7%)119.2 V146.49 V (70.43%)73062.6 WDrop/Amp High
3 AWG26.67 mm²100 A70.43 V (33.86%)137.6 V116.17 V (55.85%)57940.5 WDrop/Amp High
2 AWG33.62 mm²115 A55.87 V (26.86%)152.1 V92.15 V (44.3%)45962.9 WDrop/Amp High
1 AWG42.41 mm²130 A44.29 V (21.29%)163.7 V73.05 V (35.12%)36436.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A35.11 V (16.88%)172.9 V57.92 V (27.85%)28889.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A27.85 V (13.39%)180.1 V45.95 V (22.09%)22916.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A22.09 V (10.62%)185.9 V36.45 V (17.52%)18177.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A17.52 V (8.42%)190.5 V28.9 V (13.89%)14414.9 WDrop/Amp High
250 kcmil126.7 mm²255 A14.82 V (7.13%)193.2 V24.45 V (11.76%)12196.3 WDrop/Amp High
300 kcmil152.0 mm²285 A12.36 V (5.94%)195.6 V20.38 V (9.8%)10166.3 WDrop/Amp High
350 kcmil177.3 mm²310 A10.59 V (5.09%)197.4 V17.47 V (8.4%)8715.6 WDrop/Amp High
400 kcmil202.7 mm²335 A9.27 V (4.45%)198.7 V15.28 V (7.35%)7623.4 WDrop/Amp High
500 kcmil253.4 mm²380 A7.41 V (3.56%)200.6 V12.23 V (5.88%)6098.2 WDrop/Amp High
600 kcmil304.0 mm²420 A6.18 V (2.97%)201.8 V10.19 V (4.9%)5083.1 WDrop/Amp High
750 kcmil380.0 mm²475 A4.94 V (2.38%)203.1 V8.15 V (3.92%)4066.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.71 V (1.78%)204.3 V6.11 V (2.94%)3049.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 350 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 4.94V (2.38%) and delivers 203.1V at the load.

What size aluminum wire is required for 475 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.11V (2.94%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.